Operation continued
Bypass Status
Test Status
Output Relay
Environment
Description Address Value Unit
Bypass Frequency 0x0456 0-999 0.1 Hz
Bypass Number Lines 0x0457 0-9
Bypass Voltage 1 0x0458 0-9999 0.1 Voltage
Bypass Current 1 0x0459 0-9999 0.1 Amp
Bypass Power 1 0x045A 0-65534 10 Watt
Bypass Voltage 2 0x045B 0-9999 0.1 Voltage
Bypass Current 2 0x045C 0-9999 0.1 Amp
Bypass Power 2 0x045D 0-65534 10 Watt
Bypass Voltage 3 0x045E 0-9999 0.1 Voltage
Bypass Current 3 0x045F 0-9999 0.1 Amp
Bypass Power 3 0x0460 0-65534 10 Watt
Bypass Voltage 12 0x0461 0-9999 0.1 Voltage
Bypass Voltage 23 0x0462 0-9999 0.1 Voltage
Bypass Voltage 31 0x0463 0-9999 0.1 Voltage
Bypass STS Temperature 0x0464 0-999 Degrees Celsius
Reserved 0x0465
Reserved 0x0466
Description Address Value Unit
Test Result 0x0467
0: No Test Performed
1: Test Passed
2: Test In Progress
3: General Test Fault
4: Battery Test Fault
5: Deep Battery Test Fault
6: Test Aborted
Description Address Value Unit
Number of Output Relay 0x0468
0: Not Available
>0: Available (<=99)
Description Address Value Unit
Temperature 0x0469 0-999 Degrees Celsius
Humidity 0x046A 0-999
Relay 1 0x046B 0: Off, 1: On
Relay 2 0x046C 0: Off, 1: On
Relay 3 0x046D 0: Off, 1: On
Relay 4 0x046E 0: Off, 1: On
Reserved 0x046F
Reserved 0x0470