Operation continued
Power Module General Status
Power Module PFC Status
Description Address Value Unit
Power Module ID / General Status 0x048C Lo: ID (1-4), Hi: Status
Power Module ID / General Status 0x048D
Power Module ID / General Status 0x048E
Power Module ID / General Status 0x048F
Reserved 0x0490
Reserved 0x0491
Power Module General Status:
B0: The power module exists or the power module is powered
B1:
B2:
B3:
B4:
B5:
B6:
B7: Fault shutdown
Description Address Value Unit
Power Module ID 0x0492 1-4
PFC Status 0,1 0x0493 Lo: Status 0, Hi: Status 1
Power Module ID 0x0494
PFC Status 0,1 0x0495
Power Module ID 0x0496
PFC Status 0,1 0x0497
Power Module ID 0x0498
PFC Status 0,1 0x0499
Reserved 0x049A
Reserved 0x049B
Reserved 0x049C
Reserved 0x049D
PFC Status:
B0: PFC fuse open shutdown
B1: PFC over temperature warning
B2: PFC over temperature shutdown
B3: DC bus over voltage warning
B4: DC bus over voltage shutdown
B5: DC bus under voltage warning
B6: DC bus under voltage shutdown
B7: PFC circuit general fault
B8: Fan failure
B9: TBD
B10: TBD
B11: TBD
B12: Inner communication failure
B13: TBD
B14: TBD
B15: Not calibrated (used to indicate whether the power module has been calibrated)