Operation continued
Holding Register (Range 0x0300 - 0x0321, Read Function 0x03, Write Function 0x06) continued
Input Register (Range 0x0400 - 0x051C, Read Function 0x04) Rating Value
Description Address Value Unit
UPS Periodic Auto-Test 0x030D
1: Disable
2: Daily
3: Weekly
4: Bi-Weekly
5: Monthly
Buzzer Test 0x030E 1-99 Seconds
UPS Boot Delay 0x030F 0-999 Seconds
Bypass Freq. Tolerance 0x0310 5-50 0.1 Hz
Select Output Voltage 0x0311 0-999 Voltage
Test Time 0x0312 1-60 Minutes
Test Voltage 0x0313 0-999 Voltage
Reserved 0x0314
Reserved 0x0315
External Battery Pack 0x0316 0-10
Dry Contact W1 0x0317
Dry Contact W2 0x0318
Dry Contact W3 0x0319
Dry Contact W4 0x031A
Dry Contact W5 0x031B
Dry Contact W6 0x031C
Bypass Low Transfer Voltage 0x031D 0-999 Voltage
Bypass High Transfer Voltage 0x031E 0-999 Voltage
Bypass Voltage Tolerance 0x031F 0-999 Voltage
Dry Contact Input Status 1 0x0320
Dry Contact Input Status 2 0x0321
Note: Your UPS may not support all fields.
The Read Input Registers function code is used to read 1-125 contiguous input registers in a remote device. The starting register address and number of
registers is specied by the request Protocol Data Unit. Addresses start at 0 and registers numbered 1-16 address as 0-15.
Description Address Value Unit
Series 0x0400
0: T
1: H
2: NT
3: NH
Rating Input Voltage 0x0401 0-999 Voltage
Rating Input Frequency 0x0402 0-999 0.1 Hz
Rating Output Voltage 0x0403 0-999 Voltage
Rating Output Frequency 0x0404 0-999 0.1 Hz
Rating VA 0x0405 0-65534 10 VA
Rating Output Power 0x0406 0-65534 10 Watt
Low Battery Time 0x0407 0-99 Minutes
Low Tx Voltage Point 0x0408 0-999 Voltage
High Tx Voltage Point 0x0409 0-999 Voltage
Low Tx Voltage Upper Bound 0x040A 0-999 Voltage
Low Tx Voltage Lower Bound 0x040B 0-999 Voltage
High Tx Voltage Upper Bound 0x040C 0-999 Voltage
High Tx Voltage Lower Bound 0x040D 0-999 Voltage