Datasheet

Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16A
Nominal Input Voltage(s) Supported 110V AC; 120V AC
UPS Input Connection Type 5-20P
Input Circuit Breakers 30A
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3
UPS Input Cord Length Details Built-in
Recommended Electrical Service 20A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4.5 min. (1600w)
Half Load Runtime (min.) 14 min. (800w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
Expandable Runtime Description
BP48V24-2U
(limit 2 w/ 48VDCSPLITTER)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable sealed, flame retardant, non-spillable batteries
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 150
Undervoltage Correction 2% output voltage regulation during undervoltages to 80
Severe Undervoltage Correction 2% output voltage regulation during undervoltages to 65 (under 70% load only)
USER INTERFACE, ALERTS & CONTROLS
Switches 2 switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
3 / 5