Datasheet
SmartOnline 110-120V 2.2kVA 1.6kW On-Line
Double-Conversion UPS, Extended Run, SNMP,
Webcard, Tower, USB, DB9 Serial
MODEL NUMBER: SU2200XLA
Description
Tripp Lite's Smart Online SU2200XLa on-line, double conversion UPS protects critical server, networking or
telecommunications equipment from blackouts, brownouts, voltage fluctuations and surges in an attractive
all-black upright tower form factor. Large capacity 2200VA/1600W UPS continuously converts incoming AC to
DC, then back to perfect sine wave AC output at 120V AC (+/-2%). Removes harmonic distortion, fast electrical
impulses, frequency fluctuations and other hard-to-solve power problems not addressed by other UPS systems.
True sine wave output and zero transfer time offers guaranteed compatibility with all equipment types. Includes 7
UPS supported outlets. 2 three-outlet load banks can be independently controlled via software interface to
selectively reboot remote equipment or automatically shed less critical loads to extend battery runtime for the most critical equipment. Battery support can be
extended with the addition of external battery packs. Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port for unattended
shutdown, remote control and monitoring of UPS system and power data. Network management interfaces support simultaneous communications via USB
port, DB9 serial port and SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto shutdown features
of Windows and Mac OS X. Includes Tripp Lite's PowerAlert UPS Power Management Software. Compatible with Tripp Lite's Watchdog Service Monitoring
and Control Software.
Features
True on-line, double conversion UPS provides a constant, pure sine wave AC output
Maintains continuous operation through blackouts, brownouts, voltage fluctuations and surges with zero transfer time
Zero transfer time, on-line, double-conversion and economy-mode operation supported
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
Accepts input voltages between 80V and 150V (65V to 150V at loads under 70%), regulating output to 120V AC +/-2%
2200VA/1600W output capacity with 7 total outlets (6 NEMA5-15/20R and 1 L5-20R)
Two built-in individually switchable load banks, each with three outets, can be controlled via software interface to selectively reboot remote equipment or
automatically shed less critical loads to extend battery runtime for the most critical equipment
Standard internal battery set provides 14 min. runtime at half load and 4.5 min. at full load
Highlights
2200VA / 2.2kVA / 1600 watt
on-line double-conversion tower
UPS
110/120V +/-2% output at
50/60Hz, high efficiency
economy mode option
Expandable runtime,
Hot-swappable battery modules
USB, RS232 & EPO ports;
support for SNMP/WEB card
options
Front panel status LEDs with
detailed load and battery metering
2 independently switchable
output load banks
NEMA 5-20P input; L5-20R &
5-15/20R outlets
Package Includes
SU2200XLa On-line
Double-Conversion UPS System
PowerAlert Software and cabling
Instruction manual with warranty
information
EPO (Emergency Power Off)
cabling
1 / 6