Datasheet

up to 500 events listed. A dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS during a
prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns the UPS output OFF and disables
Bypass output. A built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities.
Features
N+1 configuration: If maintenance is required, three self-contained, redundant 20kVA power modules can be hot-swapped with the load remaining
powered
1+1 configuration: Two SU60KX can be connected in parallel to provide either fail-safe redundancy or increased capacity
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input total harmonic distortion
(THDi)
Low THDi (less than 3%) reduces installation costs by allowing 1:1 generator sizing
Extremely efficient operation (up to 97%) saves money by reducing electricity consumption
True on-line, double-conversion UPS with IGBT technology provides pure sine wave AC output at all times
Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
60,000VA/48,000W power capacity with 3-phase, hardwire input/output connections
Wide input voltage correction range: 173-300V/276-477V AC
Precision +/-1% output voltage regulation
Included battery modules (Models BP480V26B) are housed in a separate, stand-alone hardwired external battery compartment (required for UPS
operation/backup battery support)
Battery runtime can be extended with additional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C; order separately)
Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS
Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
Accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more
Emergency Power Off button turns UPS output OFF and disables Bypass output
Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 60000
Output kVA Capacity (kVA) 60
Output Watt Capacity (Watts) 48000
Nominal Output Voltage(s)
Supported
220/380V; 230/400V; 240/415V; 3-Phase Wye
Frequency Compatibility 50 / 60 Hz
Output Receptacles Hardwire
Output AC Waveform (Battery Mode) Pure Sine wave
Output (VA) 60000
Output (Watts) 48000
2 / 5