Datasheet

Transfer Time (Line Power to
Battery Mode)
Zero transfer time: True on-line UPS continuously converts incoming AC to DC, then back to AC. When line power
is interrupted, UPS maintains continuous output from battery reserves with absolutely no disruption in output AC
power
Low Voltage Transfer to Battery
Power
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power
High Voltage Transfer to Battery
Power
Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire,
wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power
SPECIAL FEATURES
Cold Start Inverter can be cold-started via the control panel to enable temporary AC output during a power failure
CERTIFICATIONS
UPS Certifications CE
Certifications CE (EN62040-1-1)
WARRANTY
Product Warranty Period
(International)
2-year limited warranty
Product Warranty Period (Mexico) 1-year limited warranty
Product Warranty Period (Puerto
Rico)
2-year limited warranty
Optional Coverage Extended warranties and on-site service contracts available for select opportunities; contact Tripp Lite for details
© 2015 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement.
Specifications are subject to change without notice. Photos may differ slightly from final products.
5 / 5