ATM INSTALLATION FOR A CCESSIBILITY
Figure 308.2.1 Unobstructed Forward Reach
308.2.2 Obstructed High Reach. Where a high forward reach is over an obstruc-
tion, the clear floor space shall extend beneath the element for a distance
not less than the required reach depth over the obstruction. The high for-
ward reach shall be 48 inches (1220 mm) maximum where the reach depth
is 20 inches (510 mm) maximum. Where the reach depth exceeds 20 inches
(510 mm), the high forward reach shall be 44 inches (1120 mm) maxi-
mum and the reach depth shall be 25 inches (635 mm) maximum.
Figure 308.2.2 Obstructed High Forward Reach
308.3 Side Reach.
308.3.1 Unobstructed. Where a clear floor or ground space allows a parallel ap-
proach to an element and the side reach is unobstructed, the high side
reach shall be 48 inches (1220 mm) maximum and the low side reach
shall be 15 inches (380 mm) minimum above the finish floor or ground.
EXCEPTIONS: 1. An obstruction shall be permitted between the clear floor or
ground space and the element where the depth of the obstruction is 10 inches (255
mm) maximum.
2. Operable parts of fuel dispensers shall be permitted to be 54 inches (1370 mm)
maximum measured from the surface of the vehicular way where fuel dispensers are
installed on existing curbs.
13