Specifications

8D-GEL DATA SHEET
8D-GEL _TRJNRE_DS_0113
for Renewable Energy and Backup Power Applications
Page 1 of 2
MODEL: 8D-GEL
DIMENSIONS: inches (mm)
BATTERY: VRLA GEL
MATERIAL: Polypropylene
PRODUCT SPECIFICATIONS
CHARGING INSTRUCTIONS
CHARGER VOLTAGE SETTINGS (AT 77°F/25°C)
System Voltage 12V 24V 36V 48V
Absorption Charge 14.1 – 14.4 28.2 – 28.8 42.3 – 43.2 56.4 – 57.6
Float Charge 13.5 27 40.5 54
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant
under or overcharging will damage the battery and shorten its life as with any battery.
TERMINAL CONFIGURATIONS
5 LT L-Terminal
Terminal Height Inches (mm)
1-3/4 (43)
Torque Values in-lb (Nm)
100 – 120 (11 – 14)
Through-hole Diameter (mm)
3/8 (10)
OPERATIONAL DATA
Operating Temperature Self Discharge
-4°F to 113°F (-20°C to +45°C). At temperatures
below 32°F (0°C) maintain a state of charge
greater than 60%.
Less than 3% per month
depending on storage
temperature conditions.
BCI
GROUP
SIZE
TYPE
CAPACITY
A
Amp-Hours (AH)
ENERGY
(kWh)
VOLTAGE
TERMINAL
Type
D**
DIMENSIONS
B
Inches (mm)
WEIGHT lbs.
(kg)
2-Hr
Rate
5-Hr
Rate
10-Hr
Rate
20-Hr
Rate
48-Hr
Rate
72-Hr
Rate
100-Hr
Rate
100-Hr
Rate
Length Width Height
C
DEEP-CYCLE GEL BAT TERIE S
8D 8D-GEL 146 188 207 225 240 255 265 3.18 12 VOLT 5 21-1/16 (534) 11 (279) 10-13/16 (233) 161 (73)
CHARGING TEMPERATURE COMPENSATION
.028 VPC for every 10°F (5.55°C) above or below 77°F (25°C) (add .028 VPC for every 10°F (5.55°C) below 77°F and subtract .028 VPC for every 10°C above 77°F).
EXPECTED LIFE VS. TEMPERATURE
Chemical reactions internal to the battery are driven by voltage and temperature. The higher the battery temperature, the faster chemical reactions will
occur. While higher temperatures can provide improved discharge performance the increased rate of chemical reactions will result in a corresponding loss of
battery life. As a rule of thumb, for every 10°C increase in temperature the reaction rate doubles. Thus, a month of operation at 35°C is equivalent in battery
life to two months at 25°C. Heat is an enemy of all lead acid batteries, FLA, AGM and gel alike and even small increases in temperature will have a major
inuence on battery life.
Made in the USA
A. The amount of amp-hours (AH) a battery can deliver when discharged at a constant rate at 77°F (25°C) and maintain a voltage above 1.75 V/cell. Capacities are based on peak performance.
B. Dimensions are based on nominal size. Dimensions may vary depending on type of handle or terminal.
C. Dimensions taken from bottom of the battery to the highest point on the battery. Heights may vary depending on type of terminal.
D. Terminal images are representative only.
Trojan’s Battery testing procedures adhere to both BCI and IEC test standards.
•• Additional Terminals Available

Summary of content (2 pages)