Supplementary Operating Manual GB/en Explosion-proof fire damper Type FKRS-EU according to Declaration of Performance DoP / FKRS-EU / DE / 004 Read the instructions prior to performing any task!
TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn, Germany Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202-265 E-mail: trox-de@troxgroup.de Internet: http://www.troxtechnik.
Table of contents 1 General information ........................................ 4 2 Safety and correct use .................................... 5 3 Technical data .................................................. 6 3.1 FKRS-EU with explosion-proof spring return actuator ........................................... 6 3.2 ATEX areas of application ......................... 7 4 Electrical connection ...................................... 5 Functional test ............................................
General information 1 General information About this supplementary operating manual This supplementary operating manual describes the following explosion-proof variants of the fire damper: FKRS-EU with spring return actuator ExMax-15-BF-TR FKRS-EU with spring return actuator RedMax-15-BF-TR To ensure correct functioning of the fire damper, it is essential to read the provided supplementary operating manual before starting any work, and to comply with it.
Safety and correct use 2 Safety and correct use General information regarding safety The fire damper may be used in supply air or extract air systems in areas with potentially explosive atmospheres. Only specialist personnel are allowed to perform the described work on the fire damper. Only skilled qualified electricians are allowed to work on the electrical system.
Technical data FKRS-EU with explosion-proof spring return actua... 3 Technical data 3.1 FKRS-EU with explosion-proof spring return actuator Dimensions and weight Fig. 1: FKRS-EU with explosion-proof spring return actuator 1.1 1.2 1.4 1.5 1.8 10.6 Enclosure Damper blade with seal Travel stop for CLOSED position Inspection access (12 mm) Lip seal ExMax spring return actuator, alternative* 10.7* 10.
Technical data ATEX areas of application 3.
Electrical connection 4 Electrical connection General safety notes Wiring example for ExMax or RedMax spring return actuator DANGER! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. – – Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment.
Electrical connection Wiring example for TROXNETCOM Fig.
Functional test FKRS-EU with ExMax or RedMax spring return actua... 5 Functional test General During operation at normal temperatures, the damper blade is open. A functional test involves closing the damper blade and opening it again. The exact procedure depends on the type of release mechanism. WARNING! Risk of injury from the release mechanism or from a moving damper blade. Do not touch the release mechanism or reach into the fire damper while actuating the release mechanism. 5.
Functional test FKRS-EU with ExMax or RedMax spring return actua... Opening/closing the fire damper using the crank handle Fig. 7: Functional test (without power supply) DANGER! Danger due to malfunction of the fire damper. If the damper blade has been opened by means of the crank handle (without power supply), it will no longer be triggered by a temperature increase, i.e. in the event of a fire. In other words, the damper blade will not close. To re-establish its function, connect the power supply.
Explosion-proof fire damper Type FKRS-EU