Operating Instructions and Installation Instructions
16
Trouble-shooting list
 Fault    Cause    Rectification
No LED illuminates after 
switching on.
No operating voltage.
Device fuse or vehicle fuse 
defective.
If window switch present – 
window above cowl open.
–
–
–
  Check 12 V battery voltage, charge battery if necessary.
Check all electrical connections and lines.
Check equipment 1.6 A fuse (see fuses) or vehicle fuse, 
 replace fuse if necessary.
Close window.
–
–
–
–
Red LED illuminates 
approx. 15 sec. after 
 switching boiler on.
Gas cylinder empty.
Gas cylinder or quick-clo-
sure valve in the gas line is 
closed.
Combustion air infeed or 
exhaust gas outlet closed.
Battery voltage is too low 
< 10.5 V.
–
–
–
–
Replace gas cylinder.
Open valves and check gas infeed.
Remove the cap from the cowl or open the deck cowl.
Check openings for soiling (slush, ice, leaves etc.) and 
 remove if necessary.
Charge battery!
–
–
–
–
–
After a long period of opera-
tion, boiler switches to fault 
and red LED illuminates.
Overtemperature monitor 
has activated.
Gas pressure regulator 
iced up.
Butane content in the gas 
cylinder too high.
Battery voltage is too low 
< 10.5 V.
–
–
–
–
To unlock, switch device off, allow to cool and then switch 
on again.
Use de-icing system controller (Eis-Ex).
Use propane. (At temperatures below 10 °C in particular, 
butane is unsuitable for heating purposes.)
Charge battery!
–
–
–
–
Green and red LEDs 
 illuminate as soon as boiler is 
 switched on.
Faulty electronic system.– Please contact the Truma Service Centre.–
Electric operation: 
The water does not become 
warm.
Operation without water; 
over-temperature fuse cuts 
off the heating element.
– Switch off, wait 10 minutes, fill with water, switch on.–
Water supply
Water taking an extremely 
long time to heat up.
Water container furred.– Descale water system (see maintenance).–
Water running out, cannot fill 
boiler.
Safety/drain valve open.– Close safety/drain valve.–
Cannot empty boiler, even 
though safety/drain valve
is open.
Water dripping from draining 
connection of safety/drain 
valve.
Safety/drain valve draining 
connection blocked.
Venting hose is closed.
The elbow connection on 
the boiler is twisted.
Water pressure too high.
–
–
–
–
Check opening for soiling and remove if necessary.
Check opening (see above).
Check hose for kinks and remedy.
The venting hose on the elbow connection needs 
to point upwards.
Check pump pressure (max. 2.8 bar). If connected to a 
central water supply (rural or urban connection), a pressure 
reducer must be used, which will prevent pressures higher 
than 2.8 bar entering the boiler.
–
–
–
–
–
If these measures do not remove the failure, please contact the Truma Service Centre.










