Installation Manual

Reader Connection
Using the recommended cables, splice the cable together with the pigtail of the reader and seal the splice. Route
the cable from the reader to the host module. Connect the cable to the module port according to the required
operation, as shown in the connection diagrams that follow.
The recommended cable types for RS-485 are:
Belden 9842 or equivalent
24 AWG twisted pair with characteristic impedance of 120ohm
The recommended cable types for Wiegand are:
22 AWG alpha 5196, 5198, 18 AWG alpha 5386, 5388
Warning: The reader outputs D0 (green wire) and D1 (white wire) can switch to a maximum capacity of 50mA.
Exceeding this amount will damage the output.
Reader Pigtail
TSL readers have a shielded 8-wire pigtail wiring loom with a Hirose socket plug for connection to the reader.
1 2
3 4
5 6
7 8
9 0
X
Color Wire Description
Red 12VDC+ positive
Black 12VDC- negative
Green Wiegand D0 (Data 0)
White Wiegand D1 (Data 1)
Brown Wiegand LEDcontrol
Blue Wiegand beeper control
Yellow RS-485 A
Violet RS-485 B
Shield Shield (drain) wire
TSL Multi-Technology Card Reader | Installation Manual 20