Installation Manual
Table Of Contents
- Introduction
- Reader Editions
- Reader Accessories
- MIFARE Technology
- Installation Requirements
- Mounting
- Reader Connection
- Programming the Card Reader
- Technical Diagrams
- Technical Specifications
- New Zealand and Australia
- European Standards
- UK Conformity Assessment Mark
- UL and ULC Installation Requirements
- FCC Compliance Statements
- Industry Canada Statement
- Disclaimer and Warranty
Shield Connection
1.
Connect the reader pigtail shield and cable shield wires together at the reader pigtail splice.
2. Connect the cable shield to a suitable earth point. Do not connect the shield to a ground or AUX connection.
The reader pigtail shield wire is not terminated inside the reader.
1 2
3 4
5 6
7 8
9 0
X
Important:
⦁ The card reader must be connected to the module port using a shielded cable.
⦁ The shield must only be connected at one end of the cable in the metallic enclosure (frame grounded).
⦁ Do not connect the cable shield to an AUX-, 0V or V- connection on the module.
⦁ Do not connect the cable shield to any shield used for isolated communication.
⦁ The reader pigtail shield and cable shield wires should be joined at the reader pigtail splice.
⦁ Do not terminate the reader shield wire inside the reader.
TSL Multi-Technology Card Reader | Installation Manual 21