Tufvassons has a wide range of transformers and over fifty years’ experience of making
them ourselves. We offer power supply for environments that set high requirements on
isolation and safety, the energy sector for example. We help you to make the correct
choice, and if you need a product that is not available, we ensure it is made.
When there are especially high
requirements for isolation
The transformer is used when there are greater demands on
isolation between mains voltage and safety extra-low voltage
than normal. It fulfils isolation category III (>4kV), has protective
separation between the primary and secondary windings and is
adapted for supplying SELV- and PELV systems. The output
voltage is stable and the transformer is ideal for distribution
boards and standard enclosures with four modules. Naturally,
the product also has short-circuit and overload protection, as
well as complying with the insurance companies' requirement for
self-extinguishing plastic in the housing.
Type: PSLR 30
Part. no.: 8924-0001 E-number: 52 142 54
Input voltage: 180-264V, 47-63 Hz N - L
Output voltage: 24 V dc
Rated power: 30 VA (1.3A)
Standby: < 0.3 W
Linearity: < 0.1 % at ± 10% input voltage variation
Ripple: 200 mV
t-t
Efficiency: > 80 %
MTBP: 50,000 h at 70 % load at 25ºC
Weight: 0.17 kg
Encapsulation class: IP40
Insulation class: 4.2 kV
Ambient temperature: max. 40
o
C
Design: - Transformer potted in hard-setting plastic, with grey encapsulation made from impact resistant, self extinguishing
thermoplastics.
- Double insulated (earth connection not required).
- Short circuit and overload protection.
- Primary terminal 2-pole 2.5 mm² max. torque 0.25 Nm.
- Secondary terminal 2-pole 2.5 mm² max. torque 0.25 Nm.
Mounting: Snap fastening on 35 mm DIN-rail in cubicle or standard box, alternatively wall mounting with screw.
Manufacturing standard: Security: EN 61558-1; EN 61558-2-16
Emissions: EN 61,000-6-3
Immunity: EN 61,000-6-2
Other information: If required for the installation in question, the transformer must be connected by an all-pole switch in permanent
installations.