Cut Sheet

Edition: 12 / 00
Thermal Circuit Breaker W58
Electrical data
Calibration will continuously carry 100% of rating
may trip at 101...144%, but must trip at 145% of rating at +25°C
Maximum operating voltage 50 Vdc; 250 Vac 50/60Hz
Interrupt capacity 2000 A at 50 Vdc
1000 A at 250 Vac 50/60Hz
Resettable overload capacity 10x rated current
Dielectric strength > 1500 Vrms
· 0.5...25 A ratings
· Cannot be manually tripped
· Push button to reset breaker
UC Recognized as supplementary protectors
Technical data of approved types on request
F0215-A
Typical resistance vs. current rating
Current rating Max. resistance Current rating Max. resistance Current rating Max. resistance
A c A c A c
0.5 5.0 5.0 0.026 10.0 0.014
1.0 1.35 6.0 0.026 12.0 0.010
2.0 0.32 7.0 0.020 15.0 0.010
3.0 0.18 8.0 0.020 20.0 0.006
4.0 0.10 9.0 0.020 25.0 0.005
Data for
ambient temperature +25°C
How to use the correction: Multiply the breaker
rating by correction factor to determine the compen-
sated rating. Calculate the overloads in terms of the
compensated rating to use the published trip curve.