User's Manual
Table Of Contents
- AMS-9040 Controller
- Contents
- To the Installer
- About the Product
- Basic Operation and Setup
- Device Connections
- Transceiver (Tx/Rx) Antenna and Antenna Communication Connections
- General-Purpose Auxiliary Connections (P27, P29, P31, P33)
- Remote Alarm Connections (P7)
- Beacon Lamp Connections (P10)
- Relay Connections (P9, P12)
- Alarm Management Connection (P41)
- RS-485 Connection (P8)
- Wired Tx Sync Connection (P2)
- Wireless AC Sync Connection (On Controller)
- RS-232 Service Connection (On Controller)
- Ped (Tx) Inhibit Connection (P26)
- Installation Features
- Service Features
- Installation Requirements
- Installation Procedure
- AC Hookup
- System Setup
- Redistributing the Load
- Special Rules for Floor Antennas
- Troubleshooting
- Fuse Replacement
- Specifications
- Declarations
- Appendix A: Auto Synchronization
4. Plug the cord into the IEC320 receptacle in the
controller housing.
5. Plug the power cord into the ac outlet. The
controller automatically senses the voltage
(100-120Vac or 200-240Vac). No adjustments
are required.
6. Return to the installation procedure.
Hardwired Cable
CAUTION: Use only copper wire.
Referring to the figure below:
1. Remove one of the three knockouts accessing
the ac connection area in the cable tray. Thread
a cable clamp into the hole.
IEC320 Receptacle
2. Route the ac cable through a cable clamp,
leaving about 15.2cm (6in) out the other side.
Tighten the clamp around the cable.
3. Expose about 5cm (2in) of insulated wires: hot,
common, and ground.
4. Using a screwdriver, connect ac wires to the
two-pin connector: white wire to N (neutral);
black wire to L (line). Connect the green wire to
the ground post on the cable tray.
5. Plug the short power cord into the IEC320
receptacle in the controller housing.
6. Return to the installation procedure.
N
L
Ground Post
CABLE TRAY
AC CONNECTION
AREA
AC Connector
CONTROLLER
AMS-9040 CONTROLLER 8200-0367-02, REV. D
INSTALLATION AND SERVICE GUIDE
13 of 22