C•CURE Watch Installation and Service Guide 3-5
Cabling
General cabling guidelines:
• A single common ground is required for all
system components.
• All wiring that runs through a plenum area
must be plenum rated.
• RF controller cabling should not share conduit
with mains line power cabling.
• All exposed wiring must be concealed with
raceway or similar cabling protection.
• apC/iStar RS-485 cable runs of exceptional
distance may require Belden 9842, which IS
NOT plenum rated.
• Synchronization cabling is required for RF
controllers located within 152m (500ft) of each
other, even when they are not connected to the
same system.
• Passage antenna wire loop may be exposed to
corrosive cleaning fluids; cable jacket MUST
be composed of a fluoropolymer such as FEP
Teflon or Kynar with a thickness of .3mm
(.015in.).
Wire Use Wire Type Specification Star
Con.
Daisy
Chain
Maximum
Distance
RF Controller Sync to
common terminal block
(add’l wire may be needed
between terminal blocks)
2 or 4 conductor / 22 AWG,
shielded
Belden 82723 or equiv. No Yes 305m (1000ft)
RS-485 between panel and
RF controller (are there
differences between apC
and istar?)
2 conductor / 22 AWG, shielded Belden 82761 or equiv. Yes
Multi
Drop
305m (1000ft)
RF Controller to RF
Passage Antenna
(Signal/Control)
8 conductor / 22AWG, shielded
8 conductor / 18AWG, shielded 23m (75ft)
8 conductor / 16AWG, shielded 38m (125ft)
8 conductor / 14AWG, shielded 61m (200ft)
RF Controller to RF
Passage Antenna (Power)
2 conductor / 20AWG, shielded 15m (50ft)
2 conductor / 18AWG, shielded 23m (75ft)
2 conductor / 16AWG, shielded 38m (125ft)
2 conductor / 14AWG, shielded 61m (200ft)
Wire Loop for RF Passage
Antenna Pairs
1 conductor / 18 AWG, DO NOT
use shielded wire, cable jacket must
be composed of a fluoropolymer
with a thickness of .3mm (.015in.)
N/A N/A 3m (10ft)
RF Controller to Inputs 2 conductor / 22 AWG, shielded Belden 82761 or equiv. N/A N/A 305m (1000ft)
RF Controller to Outputs 2 conductor / 18 AWG, shielded Belden 82760 or equiv. N/A N/A 305m (1000ft)
RF Controller to External
Power Supply
2 conductor / 20AWG, shielded 6m (20ft)
2 conductor / 18AWG, shielded 11m (35ft)
2 conductor / 16AWG, shielded 18m (60ft)
2 conductor / 14AWG, shielded 30m (100ft)
RF Controller ac Power
Cord
Type SJ or SJT / 18AWG 250V
rated (power cord connection not
evaluated by UL)
1.8m (6ft)
minimum
Chassis Ground Wire multi-stranded / 16AWG 250V 1.8m (6ft)
Note: To maintain UL Listing, field wiring shall not be less than 22AWG.