C•CURE Watch Installation and Service Guide 8000-2803-01, Rev. 1/A 4-11
CAUTION: A 10A, 2 pole, ganged
disconnect device, which also provides
short circuit and overload protection, and
has a minimum 3mm open circuit
clearance, in accordance with the
National Electric Code and applicable
local codes must be installed by a
licensed electrician at a location readily
accessible to the equipment.
Ein 10A, 2-poliges, gekoppeltes
Ausschalt-gerät, welches auch über
einen Kurzschluß- sowie
Überbelastungsschutz verfügt, und einen
minimum 3mm offenen Schaltabstand
aufweist, nach Übereinstimmung mit den
Nationalen Elektrischen Regelungen
sowie lokalen Regeln, muß an einem
Standort installiert werden, welcher
einfachen Zugang zum Gerät erlaubt.
1. Verify that RF controller is turned off.
2. Use knockout at bottom left corner of
enclosure to access the power connector.
3. Connect incoming ac wires to the connector for
115Vac or 230Vac operation based on the
following:
NAa Europe Pin Function
Green/Yellow Green/Yellow PE Ground
White Blue N Neutral
Black Brown L Line
4. For FCC compliance, a chassis ground wire is
required. Connect chassis ground wire from a
building ground (such as pipes or conduit) to
the chassis ground terminal in the RF
controller enclosure. Use 16AWG 250V multi-
stranded wire with maximum length 1.8m (6ft).
Cord Connection
Use one of the following installation kits.
Power Cord (NA)
Description Qty. Part No.
Txxx 1 0xxx-xxxx-01
Txxx 1 0xxx-xxxx-01
Power Cord (EU)
Description Qty. Part No.
Txxx 1 0xxx-xxxx-01
Txxx 1 0xxx-xxxx-01
CAUTION: For installation using a line
cord, the socket-outlet must be installed
near the equipment and at a location
which is easily accessible.
Für Installationen mit einem Stromkabel
muß die Steckdose an einem Standort
installiert werden, welcher einfachen
Zugang erlaubt.
1. Verify that RF controller is turned off.
2. Tighten strain relief into conduit knockout at
bottom of enclosure.
3. Thread power cord through strain relief and
secure.
4. Connect incoming ac wires to the connector for
115Vac or 230Vac operation based on the
following:
NA Europe Pin Function
Green/Yellow Green/Yellow PE Ground
White Blue N Neutral
Black Brown L Line
5. For FCC compliance, a chassis ground wire is
required. Connect chassis ground wire from a
building ground (such as pipes or conduit) to
the chassis ground terminal in the RF
controller enclosure. Use 16AWG 250V multi-
stranded wire with maximum length 1.8m (6ft).
!
!