User's Manual

Table Of Contents
apC/8X Panel Setup
apC/8X Technical Manual 5-5
S2 S2:1
a
ON
OFF*
Relay link on when door forced open
No link when door forced open
S2:2
a
ON
OFF*
Relay link on when door held
No link when door held
S2:3
a
ON
OFF*
Relay link on when apC/8X is offline
No link when apC/8X is offline
S2:6
b
ON
OFF*
Reader keypad for PIN entry, if enabled
Keypad for elevator floor selection, if enabled
S2:7 ON
OFF*
apC/8X ignores card misreads
apC/8X reports misreads
S2:8 ON
OFF*
AUX port for local printout
AUX port for apC/8X test program
S3
S3:1
b
ON
OFF*
Card entry through keypad enabled
Card entry through keypad not enabled
S3:2 ON
OFF*
Optional LED access pattern enabled at reader
Normal LED access pattern enabled at reader
S3:3
b
ON
OFF*
Card numbers less than or equal to 65535 (16 bit)
Card numbers greater than 65535 (32 bit)
S3:4
b
ON
OFF*
Activate/deactivate dates are stored
Activate/deactivate dates are not stored
S3:5
b
ON
OFF*
Space reserved in card record for local anti-passback
No space reserved in card record for local anti-passback
S3:6
b
ON
OFF*
Space reserved in card record for elevator control
No space reserved in card record for local elevator control
S3:7 ON
OFF*
Magnetic stripe encryption used
No Magnetic stripe encryption used
S3:8
b
ON
OFF*
Reverse card swipe signals duress
Duress alarm disabled
Table 5.1: apC/8X DIP Switch Settings
Switch
Setting
(* = Default)
System Feature