Setting Up the apC/8X Main Panel
5-10 apC/8X Technical Manual
S3:2
Set switch S3:2 to OFF to use the default access LED pattern on all readers.
Set this switch to ON to cause the green LED to light solid (no flash) for an
access grant or door unlock. An access deny causes the red LED to flash
rapidly for two seconds.
S3:3–S3:8
These switches are NOT used with C•CURE 800/8000. Setting them has no
effect on C•CURE 800/8000 systems.
S4 and S5
Use rotary switches S4 and S5 to set the apC/8X’s unique 2-digit hex address.
Each apC/8X on an RS-485 chain must have a unique address.
S6:1–S6:8
Use switches S6 and switch S11 to establish RS-232 and RS-485 serial
connections with the host.
Refer to Table 5.4, Table 5.5, and Table 5.6 for specific switch settings.
Note: Set switches S6:5 and S:6-6 to ON when the apC/8X is the last
unit in an RS-485 daisy chain (unit is terminated).
S7
Switch 7 is a momentary push button that resets the apC/8X. During reset, the
apC/8X performs a self-test and sends the test results to the control system. If
S1:1 is set, the database is also cleared.
S8:1–S8:8
These switches are NOT used with C•CURE 800/8000. Setting them has no
effect on C•CURE 800/8000 systems.
S9:1
S9:1 should always be ON. This switch is factory preset to ON to select the
M68306A processor.