Re-Select Model allows the units model information to be
modified. Changing the units model completely
reprograms available zones, relay assignments, DC output
assignments etc.
To access Re-Select Model
1. Press to select “Re-Select Model”.
2. Press .
To change model setting
3. Press to select “Model=” and press . “Model” will
begin to flash.
4. Press or to scroll through each available model.
5. Press to confirm. While processing, the will
momentarily change to .
To exit Re-Select Model, press to select “Return to
Menu” and press to confirm. (Power cycling unit is
recommended after re-selecting model.)
Factory Wi Fi
The Factory Wi-Fi option is only used in manufacturing
and should always be OFF.
1. Press to selectFactory Wi Fi.
2. Press .
3. Press or selectOFF.
To exit the Factory Wi Fi menu press to select “Return
to Menu” and press to confirm outputs.
Set Points
The Set points menu contains options to modify both the
Zone and Evap set points. Changes to the zone set point
will be reflected on the main screen. Changes to the evap
set point alter the temperature the evaporator needs to
meet during a defrost cycle.
To access Set Points
1. Press to select “Set Points.
2. Press .
3. Press and to scroll through available set points.
To change set points
4. Press , the selected set point will begin to flash.
5. Press or to modify the value.
6. Press to confirm setting.
To exit the Set Points menu, press to select “Return to
Menu” and press to confirm.
Fan Delay (excludes ZWC)
Up
Select
Down
RETURN TO MENU
FACTORY WiFi
OFF
Up
Select
Down
RETURN TO MENU
SET POINTS
ZONE = 3°C
EVAP = 5°C
Up
Select
Down
RETURN TO MENU
FAN DELAY
FAN DELAY ON = 1
FAN DELAY OFF = 2
*
53