Soft Start with Bypass Contactor-6kW User Manual KEY FEATURES • Soft start • Pedestal • Easy to install X20012 Issue 1 Date 4/08/16 Page 1 of 7
TECHNICAL SPECIFICATION Supply Voltage 230VAC +/- 10% 50/ 60 Hz Switching Capacity 6kW Max. Ramp On-Time 1 – 5 Seconds Pedestal Value 0 – 40% (Conduction Angle) Current Consumption (control circuit) 20mA Terminals 6.0mm2 Rising Clamp Operating Temperature -20 to 40°C Protection Rating IP65 Gland Diameter Max Cable Entry 2.
WIRING It is recommended that installation and maintenance of this equipment should be done with reference to the current edition of the I.E.E. wiring regulations (BS7671) by suitably qualified/trained personnel. These regulations contain important requirements regarding safety of electrical equipment (for International Standards refer to I.E.C/ directive IEC950). Warning! Isolate the mains supply before commencing any work on the unit. Failure to do so could result in serious injury or fatality.
WIRING DIAGRAM
MOUNTING TEMPLATE IMPORTANT! When wall mounting, the unit must be orientated with the cable glands facing down. Use these template dimensions to locate the 4 mounting-hole centres prior to drilling. IMPORTANT! Drilling of any holes through the enclosure will immediately invalidate the warranty of the unit. The unit MUST be orientated with the cable glands facing down.
TROUBLESHOOTING Warning! Isolate the mains supply before commencing any work on the unit. Failure to do so could result in serious injury or fatality. Problem: System doesn’t Start Solution: • Check the mains supply to the unit is switched on. • Check Enable Link Is Fitted. • Check the LINE and LOAD wiring connections to the unit and the Load. • Contact your supplier.
PRODUCT APPLICATION • Transformers • Motors • Compressors • All resistive loads Southport Business Park, Wight Moss Way, Southport, PR8 4HQ Tel +44 (0)1704 516500 Fax: +44(0)1704 516501 Email:sales@united-automation.com Web:www.united-automation.