Datasheet
ORDER CODE : A72301 VAC2-3/RFI
SPECIFICATIONS
Maximum RMS on-state current
Minimum operating current
3A
100mA
Peak one cycle surge @ 10mS 150 A
I
2
t for fusing 100 A
2
s
Isolation voltage 2500V rms
Maximum recommended unit temperature 70ºC
Mains supply +/-10% @ 50/60Hz 230V ac
Output Range 0-98%
Minimum Set Speed Range 0-98%
FUSING & WIRING:
It is recommended to use
semiconductor (fast acting) type
fuses or circuit breakers
(Semiconductor - MCB) for unit
protection. On initial ‘switch on’
some loads may need an increased
Factor of Safety (F of S) for unit
and/or device protection. (See the
SRA Datasheet for further
information).
Installation and maintenance of this
equipment should be done with
reference to the current edition of
the I.E.E. wiring regulations
(BS7671) by suitably
qualified/trained personnel. The
regulations contain important
requirements regarding safety of
electrical equipment (For)
International Standards refer to
I.E.C/ directive IEC 950).
FEATURES
• Infinitely variable 0-98% output.
• Minimum Set Speed Adjuster
• Single hole fixing.
• Rugged and compact.
• Large triac for inrush protection.
• Integral RC Snubber
• Integral EMC filtering
DESCRIPTION
This compact variable phase angle regulator is of open construction and is suitable for 230V operation, driving up to 3Amp single phase
mains driven inductive loads, such as induction motors, fans & pumps. It gives fully adjustable voltage outputs from zero to maximum.
The controller has an integral RC Snubber network for control of inductive loads and a Minimum Set Speed adjuster (multi-turn cermet) to
allow the designer/installer to fix a minimum output voltage level to prevent a motor being driven too slowly.
An integral choke/capacitor RFI circuit enables to controller to meet current EMC standards for emissions.
The large Triac enables the unit to handle high inrush currents with ample safety margin on industrial installations. An adhesive backed silver
label and hairline knob, are optional extras, for front panel mounting.
APPLICATION
Suitable for most simple mains driven motors & fans
VAC2-3/RFI
X10693
RECOMMENDATIONS
Other documents available on request, which may be appropriate for your application:-
CODE IDENTITY DESCRIPTION
X10229 RFI Single Phase Filtering recommendations - addressing EMC Directive
X10213 ITA Interaction, uses for phase angle and for burst fire control.
X10255 SRA Safety requirements - addressing the Low Voltage Directive
(LVD) including :- Thermal data/cooling ; “Live” parts warning & Earth
requirements; Fusing recommendations.
AP02/4 COS UAL Conditions of sale.
SINGLE-PHASE
FAN CONTROLLER
3 Amps Maximum
UNITED AUTOMATION LIMITED
Southport Business Park Tel: 0044 (0) 1704 – 516500
Wight Moss Way Fax: 0044 (0) 1704 – 516501
Southport, PR8 4HQ enquiries@united-automation.com
ENGLAND www.united-automation.com
Page No. 1 of 1 Issue 2 Date 15/01/18
RoHS Compliant
Directive