Installation Instructions Chapter 3

UHF Analog Driver/Transmitter Chapter 3, Site Considerations,
Installation and Setup Procedures
LX Series, Rev. 0 3-1
Chapter 3
Site Considerations, Installation and Setup Procedures
There are special considerations that
need to be taken into account before the
Innovator LX Series analog
driver/transmitter can be installed. For
example, if the installation is completed
during cool weather, a heat-related
problem may not surface for many
months, suddenly appearing during the
heat of summer. This section provides
planning information for the installation
and set up of the driver/transmitter.
3.1 Site Considerations
The transmitter requires an AC input line
of 117 VAC/220 VAC @ 5 amps for the
10W transmitter and driver or 117
VAC/220 VAC @ 10 amps for the 100W
Transmitter. The transmitter is factory
set for 110 VAC or 230 VAC operation.
The LX Series Analog Transmitters are
designed and built to provide long life
with a minimum of maintenance. The
environment in which they are placed is
important and certain precautions must
be taken. The three greatest dangers to
the transmitter are heat, dirt, and
moisture. Heat is usually the greatest
problem, followed by dirt, and then
moisture. Over-temperature can cause
heat-related problems such as thermal
runaway and component failure. Each
amplifier module in the transmitter
contains a thermal interlock protection
circuit that will shut down that module
until the temperature drops to an
acceptable level.
A suitable environment for the
transmitter can enhance the overall
performance and reliability of the
transmitter and maximize revenues by
minimizing downtime. A properly
designed facility will have an adequate
supply of cool, clean air, free of airborne
particulates of any kind, and no
excessive humidity. An ideal environment
will require temperature in the range of
40° F to 70° F throughout the year,
reasonably low humidity, and a dust-free
room. It should be noted that this is
rarely if ever attainable in the real world.
However, the closer the environment is
to this design, the greater the operating
capacity of the transmitter.
The fans are designed and built into the
transmitter will remove the heat from
within the modules, but additional means
are required for removing this heat from
the building. To achieve this, a few issues
need to be resolved. The first step is to
determine the amount of heat to be
removed from the transmitter room.
There are generally three sources of heat
that must be considered. The first and
most obvious is the heat from the
transmitter itself. This amount can be
determined for a 100W transmitter by
subtracting the average power to the
antenna (69.5 watts) from the AC input
power (675 watts) and taking this
number in watts (605.5) and then
multiplying it by 3.41. This gives a result
of 2,065, the BTUs to be removed every
hour. 12,000 BTUs per hour equals one
ton. Therefore, a 1/4-ton air conditioner
will cool a 100W transmitter.
The second source of heat is other
equipment in the same room. This
number is calculated in the same way as
the equation for BTUs. The third source
of heat is equally obvious but not as
simple to calculate. This is the heat
coming through the walls, roof, and
windows on a hot summer day. Unless
the underside is exposed, the floor is
usually not a problem. Determining this
number is usually best left up to a
qualified HVAC technician. There are far
too many variables to even estimate this
number without reviewing the detailed
drawings of the site that show all of the
construction details. The sum of these
three sources is the bulk of the heat that
must be removed. There may be other

Summary of content (15 pages)