Chapter 8 Parameter Listing and Descriptions
Application Parameters
Application ParametersApplication Parameters
Application Parameters
Operation
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be set
to one of the following:
Option
Description
When Ultra Wizard = 1 Level/volume, 2 Pump or 3 Flow
1 = Distance (Default)
Display shows the distance from the
transducer face to the surface.
2 = Level
Display shows how
full
the vessel is.
3 = Space
Displ
ay shows how
empty
a vessel is.
When Ultra Wizard = 1 Level/Volume
5 = Volume
Display shows
volume
of the vessel.
When Ultra Wizar
d = 3 Flow
4 = OCM Head
Display shows how high the
head
is.
5 = OCM Flow
Display shows the instantaneous
flow
.
P101 Xducer (Transducer)
This parameter should be set to the transducer being used with the unit, and
can be set to one of the following:
Option
Description
When Ultra Wizard = 1 Level/volume, 2 Pump
1 = dB3
Transducer is a dB3.
Range 0.410 t
o 9.843 feet
2
= dB6 (Default)
Transducer is a dB6.
Range 0.984 to 19.685 feet
3= dB10
Transducer is a dB10.
Range 0.984 to 32.808 feet
4= dB15
Transducer is a dB15.
Range 1.640 to 49.213 feet
7 = dBS6
Transducer is a dBS6.
Range 0.656 to 19.685 feet
8 = dBMach3
Transducer is a dBMach3
. Range zero to 7.956 feet
When Ultra Wizard = 1 Level/Volume
5= dB25
Transducer is a dB25.
Range 1.969 to 82.021 feet
6 = dB40
Transducer is a dB40.
Range 3.937 to 131.234 feet