Instruction manual

Page 126
Option
Description
When Ultra Wizar
d = 3 Flow
1 = dBMach3
(Default)
Transducer is a dBMach3. Range zero to 7.965 feet
2 = dB6
Transducer is a dB6.
Range 0.984 to 19.685 feet
3= dB10
Transducer is a dB10. Range 0.984 to 32.808 feet
4= dB15
Transducer is a dB15. Range 1.640 to 49.213 feet
7 = dB
S6
Transducer is a dBS6. Range 0.656 to 19.685 feet
P102 Material
This parameter should be set to the type of material being monitored.
Option
Description
1 = Liquid
(Default)
Use for liquids and flat solid materials
2 = Solid
Solid mate
rial that is heaped or at an angle
3= Closed Tank
Use for applications within a closed vessel
or where a secondary echo response may
become focussed to create a larger echo
than the first.
Dimensions
P104 Measurement Units
This parameter sets the units you want to use for programming and display
Option
Description
1 = metres
All units of measure are
METRES
2 = cm
All units of measure are
CENTIMETRES
3 = mm
All units of measure are
MILLIMETRES
4 = feet
(Default)
All units of measure are
FEET
5 =
inches
All units of measure are
INCHES
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the empty point, in P104 Measurement Units. Note this
value affects span as well, (see important information below), so should be
set before span.