P210, P220, P230 - Relay Type
This parameter defines what type each relay should be, see the table below
for available options.
Option
Description
0= Not In Use (Default)
Relay not in use or programmed and LED
will always be off.
1= Alarm
Relay is programmed as an alarm relay,
which will de-energise ON, and energise
OFF. This will ensure an alarm is raised
if the power fails to the unit.
2= Pump
Relay is programmed as a pump relay,
which will energise ON, and de-energise
OFF.
3= Control
Relay is programmed as a control relay,
which will energise ON, and de-energise
OFF.
4= Miscellaneous
Relay is programmed as a miscellaneous
relay, which will energise ON, and de-
energise OFF.
When Ultra Wizard =
1 Level/Volume
2= General Control
Relay is programmed as a general control
relay, which will energise ON, and de-
energise OFF.