The fourth parameter, fifth parameter and sixth parameter are set to
determine the switch points, “ON” and “OFF” for the relay and where
required the order of start. See control function, table (P211, 221, 231) for
further information.
P211, 221, 231 =1 (Time)
P213, P223, P233 - Relay Setpoint 1
This parameter determines the “Time Period” that the relay will remainON.
Relay Setpoints are entered in Minutes.
P214, P224, P234 - Relay Setpoint 2
This parameter determines the “Cycle Time ” for the operation of the relay.
Relay Setpoints are entered in Minutes.
See the appropriate relay function tables (P211, 221, 231) for further
information.
P211, 221, 231 = 2 (Step Time)
P213, P223, P233 - Relay Setpoint 1
This parameter will determine thelevel at which the relay will become active.
Relay Setpoint 1 is entered in values of Measurement Units (P104)
P214, P224, P234 - Relay Setpoint 2
Relay Setpoints are entered in Seconds to set Drive Period, the time that the
relay will remain ON
P215, P225, P235 - Relay Setpoint 3
This parameter is used to determine the Limit Time between each Drive Period.
Relay Setpoints are entered in Minutes, during which time the relay will remain
OFF.
See the appropriate relay Function tables (P211, 221, 231) for further
information.