Miscellaneous
When P210, 220, 230 = 4 (Miscellaneous)
When a relay is set to be a miscellaneous relay, the second parameter
determines its function.
P211, P221, P231 - Relay Function,
This function allows the relay to work in relation to a clock or a specific
event and will be set to activate in relation to Real Time.
O
ptions
Description
0 = Off (Default)
Relay
Off de
-
energised
1 = Clock
Relay will energise ON at a specified time
each day as set in Relay Setpoint 1 (P213,
223, 233). And turns OFF, de-energises,
after the specified On Time period as set in
Relay Setpoint 2 (P214, 224, 234)
When
Ultra Wizard = 3 Flow
then
2 = Totaliser
Relay will energise ON momentarily each
time the specified flow has passed as set in
Relay setpoint 1 (P213, 223, 2330, this
parameter sets the multiplication factor
which will be applied to the on board
totaliser (P820) to determine the switch
point of the relay. E.g. if the totaliser is set
to totalise in cubic metres and the relay is
required to provide a closure every 10,000
litres Relay setpoint 1 would be set to 10.
Relay setpoint 2 (P214, 224, 234) is used
to select the time the relay will remain
closed in seconds.
Important Information
When using a Relay to control a device at a specified time of day ensure that
the Time P932 is set correctly. And if required, enable Daylight Saving for
the appropriate time difference P970 – P979.
The third parameter has no function when miscellaneous relay is chosen
and will not be displayed.