Instruction manual

Page 143
The fourth parameter, and fifth parameter, are set to determine the switch
points, ON and OFF for the relay. See miscellaneous function table
(P211, 221, 231) for further information.
P211, 221, 231 = 1 (Clock)
P213, P223, P233 - Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which
relay will energise. Default = 00:00 (HH:MM)
P214, P224, P234 - Relay Setpoint 2
Relay Setpoints are entered in Minutes to set Time Period that the relay will
remain ON. Default = 0.00 mins.
P211, P221, P231 = 2 (Totaliser)
P213, P223, P233 - Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on board totaliser (P820)
should be multiplied by to provide a relay closure. Default = 0.00
P214, P224, P234 - Relay Setpoint 2
Relay Setpoints are entered in seconds to set the time period that the relay will
remain ON’. Default = 0.00 secs.
Common Parameters
P217, P227, P 237 - Relay Closures
The Ultra 3 will record how many times each relay is operated, this
parameter displays the number of times the relay has activated since the
relay has been in use. It can be reset with any value.
P218, P228, P238 - Relay Fail Safe
Your Ultra 3 has a general fail-safe parameter P808. However, this can be
overridden so that each individual relay has its own independent fail safe
mode.
This parameter determines what the relay will do in the event of the Fail
safe Time (P809) expiring.
Option
Description
0 = Default
Relay assumes system default mode P808
1 = Hold
Relay remains in its current state
2 = De
-
Energise
Relay will De
-
Energise
3 = Energise
Relay will Energise