Instruction manual

Page 144
Data Log Parameters
Data Log ParametersData Log Parameters
Data Log Parameters
The data log parameters contains the following information.
Totaliser Audits
When Ultra Wizard = 3 Flow
P460 to P479 Total Audits
Parameters P460-P479show the date and flow total for the last ten days, the
first on the list are the most recent and last ones are the oldest. When all ten
total audits are full the oldest is pushed out and all totals increment through
to allow the new days total to be registered in the first days total audit
parameter allocation.
Important Information
In order to ensure the accuracy of Flow during a 24 hour period, ensure that
the Time P932 is set correctly. And if required, enable Daylight Saving for
the appropriate time difference P970 – P979.
P480 Clear Logs
This parameter enables all of the Total Audits (P460 P479) to be cleared
to factory default values.
Temperature
The following parameters give information on temperature conditions seen
by the Temperature source (P852) in ºC. All of these parameters are read
only and cannot be changed, though if P852 is changed they will be reset.
P580 Minimum Temperature
This parameter displays the minimum temperature recorded.
P581 Minimum Temperature Date
This parameter displays the date when the minimum temperature was
recorded.
P582 Minimum Temperature Time
This parameter displays the time when the minimum temperature was
recorded.