Instruction manual

Page 166
mA Output Parameters
mA Output ParametersmA Output Parameters
mA Output Parameters
Range
P830 mA Range
This parameter determines the range of the mA output, from the following.
Option
Des
cription
0= Off
mA output disabled.
1= 0 to 20 mA
mA output directly proportional to the mA mode
(P831), so if the reading is 0% the output is 0 mA. If
the reading is 100% the output is 20 mA.
2= 4 to 20 mA
(Default)
mA output directly proportional to the mA mode
(P831), so if the reading is 0% the output is 4 mA. If
the reading is 100% the output is 20 mA.
3= 20 to 0 mA
mA output inversely proportional to the mA mode
(P831), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 0 mA.
4= 20 to 4 mA
mA output inversely proportional to the mA mode
(P831), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 4 mA.
Operation
P831 mA Mode
This parameter determines how the ma Output relates to what is measured.
By default it operates exactly the same as the display (P100), but it can be
set to operate as follows:
When Ultra Wizard = 1 Level/Volume
Option
Description
When Ultra Wizard = 1 Level/Volume, 2 Pump or 3 Flow
0 = Default
mA output relative to
Mode
P100
1 = Distance
mA output relative to
distance
.
2 = Level
mA output relative to
level
.
3 = Space
mA output is relative to
space
.
When Ultra Wizard = 1 Level/Volume
5 = V
olume
mA output is relative to volume (
P100 = 5
)
When Ultra Wizard = 3 Flow
4 = OCM Head
mA output is relative to
OCM
head
.
5 = OCM Flow
mA output is relative to
OCM
flow
.
6 = Average Flow
mA output is relative to
average flow