P149 Retry No.
This parameter will set the number of times the telephone number will be re-
dialled if no reply is received. If set to ‘0’ then the number will be re-dialled
continually until a reply is received, if set to ‘-1’ then number will not be re-
dialled at all. Any other value entered between 1 and 99 will determine the
number of re-dials to be attempted. Default = 0
Test Parameters
Test ParametersTest Parameters
Test Parameters
Simulation
P980 Simulate
Test mode is used to simulate the application and confirm that all parameters
and relay setpoints have been entered as expected. During simulation, there
is a choice of whether the relays will change state (hard simulation) or not
(soft simulation), but the LED’s will always change colour as programmed,
and the current output will change. If you want to test the logic of the
system that the relays are connected to then select a hard simulation, but if
you don’t want to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic
simulation will move the level up and down between empty level or the pre-
determined Start Level (P983) and Pump/Control relay switch points, if
you wish to change the direction of the level movement e.g. to go beyond
relay setpoints, this can be done by using the arrow keys. In manual
simulation, using the arrow keys will allow you to move the level up and
down as required.
The choices for you to enter are as follows.
1= Manual soft simulation
2= Automatic soft simulation
3= Manual hard simulation
4= Automatic hard simulation
To return to program mode, press CANCEL and test mode will
end.Note
Pump start delay (which by default is 10 seconds) is set to 0 during
simulation.