Instruction manual

Page 42
Parameter
Default
Description
P101 Transd
ucer
2 = dB6
Type of transducer being used.
P102 Material 1 = liquid
Material in the vessel, either liquid
or solid. If the solid lays flat then it
can be entered as liquid.
P104
Measnt. Units
4 = feet
Select units to be used for
programming measurement
information.
P105
Empty Level
19.685 feet
Distance from the face of the
transducer to the material at the
bottom of the vessel.
P106
Span
18.701 feet
Distance from the empty level (0%
full) to span (100% full).
If you have selected a Volume Application you will now be prompted to
enter details required for the calculation of volume.
Parameter
Default
Description
P600
Vessel Shape
0=Cyl. Flat
Base
Shape of vessel being monitored.
P601-P603
Vessel
Dimensions
dependant on
vessel shape
selected.
Enter Vessel dimensions as required
P605
Volume units
7 = Cubic ft. Selects volume units required.
P607
Max Volume
Read Only
Displays the calculated Volume in
P605 units.