The default values used for determining the relay setpoints, when setting
Alarms and Control relays, via the Quick Setup menu are entered as a %
of span and are as follows.
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Down
O
ne
Control 1
80%
20%
Cntl. Down Two
Control 1
Control 2
80%
70%
20%
20%
Cntl. Down Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Up
One
Contr
ol 1
20%
80%
Cntl. Up Two
Control 1
Control 2
20%
30%
80%
80%
Cntl. Up Three
Control 1
Control 2
Control 3
20%
30%
40%
80%
80%
80%
Relay
Function
Relay I.D.
On
Setpoint
Off
Setpoint
Alarm HiHi 90% 85%
Alarm High 85% 80%
Alarm Low 10% 15%
Alarm LoLo 5% 10%