To program the Vantage 100 for Example 3 Reservoir Control (pump up)
by using the Quick Setup menu proceed as follows.
If required access the Program Mode
Key in the passcode 1997 and press ENTER
Using the ‘right arrow key go to Quick Setup menu press ENTER and as
prompted, by the questions, select the relevant option and ENTER.
Question
Option
Level, Pump Up or Down
3 = Pump Up
No. of
Pumps
2 = 2 Pumps
Pump Duty
3 = Alt DutAss
Pump No. 1
1 = Set to Relay 2
Pump No. 2
2 = Set to Relay 3
No. of Alarms
1 = 1 Alarm
Type Alarm 1
2 = Low
Alarm No.1
The unit will know that only Relay 1
is available and so will automatically
set Alarm 1
to Relay 1
Xducer (P101)
2 = dB6
Measnt Units (P104)
4
=
feet
Empty Level (P105)
11.0
(
feet
)
Span (P106)
10
.0
(
feet
)
Programming is now complete and the unit can be returned to the run mode,
press CANCEL until Run Mode? Is displayed on the LCD press ENTER,
and the Vantage 100 will return to the Run Mode.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed , and entering new values to relay setpoints as required.
Alternatively the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.