Instruction manual

Page 90
Parameter
Default
Description
P823
Totaliser
Multiplier
1= /1000
Sets the factor by which the
calculated volume will be divided or
multiplied by before being displayed.
1 = /1000
3 = /10
5 = *10
7 = *1,000
9 = *100,000
2 = /100
4 = *1
6 = *100
8 = *10,000
10 = *1,000,000
The remaining parameters required to finalise the setup of your application
will follow on immediately from the above. These parameters relate to
details required to carry out the calculation for flow and will be dependent
on the Primary Measuring Device chosen and the method of calculation
chosen, please enter values for the parameters concerned as requested.
Parameter
Default
Description
P705
Max. Flow
0.000 When requested enter the known
maximum flowrate, in units of volume
(P706) and Time (P707) which occurs at
maximum head (P704)
P710
Dim. “A”
0 When requested enter, in measurement
units, P104, the required dimension.
P711
Dim. “B”
0 When requested enter, in measurement
units, P104, the required dimension.
P712
Dim. “C”
0 When requested enter, in measurement
units, P104, the
required dimension.
P713
Dim. “D”
0 When requested enter, in measurement
units, P104, the required dimension.
P717
Exponent
Dependent on
chosen PMD
Where available the Flow Oracle will
automatically enter the default exponent
value for the PMD chosen, but this can be
changed if required. When
P700 = 7 (Other), enter the exponent
value as defined by the manufacturer of
the PMD.
P718
K Factor
Enter the ‘K’ factor for the PMD,
obtained from the manufacture’s
spe
cification
, if required.