Specifications
Models:
GS8048A GS4048A
Instantaneous Power (100ms):
16970VA 8500VA
Surge Power (5 sec):
12000VA 6000VA
Peak Power (30 min):
9000VA 4500VA
Continuous Power Rating (@ 25°C):
8000VA 4000VA
Nominal DC Input Voltage:
48VDC 48VDC
AC Output Voltage (Selectable):
120/240VAC (200 to 260VAC) 120/240VAC (200 to 260VAC)
AC Output Frequency (Selectable):
60Hz (50Hz) 60Hz (50Hz)
Continuous AC Output Current (@ 25°C):
33.3AAC @ 240VAC 16.7AAC
Idle Power:
Invert mode, no load: 34W | Search: 10W Invert mode, no load: 34W | Search: 10W
Typical Efficiency:
93% 93%
CEC Weighted Efficiency:
92.5% 92.5%
Total Harmonic Distortion:
Typical: <2% | Maximum: <5% Typical: <2% | Maximum: <5%
Output Voltage Regulation:
±2% ±2%
AC Input Voltage Range (MATE3s Adjustable):
L1-N or L2-N: 85 to 140VAC L1-N or L2-N: 85 to 140VAC
AC Input Frequency Range:
@ 60Hz: 54 to 66Hz | @ 50Hz: 45 to 55Hz
Grid-Interactive Voltage Range:
L1-N or L2-N: 85 to 140VAC L1-N or L2-N: 108 to 132VAC
Grid-Interactive Frequency Range:
59.3 to 60.5Hz 59.3 to 60.5Hz
Maximum AC Input Current:
50AAC @ 240VAC 50AAC @ 240VAC
Maximum Utility Interactive Current:
30A 15A
Continuous Battery Charge Output:
115ADC 57.5ADC
Advanced Battery Charging:
Flooded, gel, AGM, lithium-ion and flow chemistry Flooded, gel, AGM, lithium-ion and flow chemistry
DC Input Voltage Range:
40 to 64VDC 40 to 64VDC
Accessory Ports:
Remote temperature sensor (included), MATE3s and HUB communications Remote temperature sensor (included), MATE3s and HUB communications
Warranty:
Standard 5 year, extended 10 year available Standard 5 year, extended 10 year available
Weight (lb/kg):
Unit: 125 / 56.7 | Shipping: 140 / 63.5 Unit: 82 / 37.2 | Shipping: 94 / 42.6
Dimensions H × W × D (in/cm):
Unit: 28 × 16 × 8.7 / 71.1 × 40.6 × 22.1 | Shipping: 34.5 × 21 × 14.5 / 87.6 × 53.3 × 36.8 Unit: 28 × 16 × 8.7 / 71.1 × 40.6 × 22.1 | Shipping: 34.5 × 21 × 14.5 / 87.6 × 53.3 × 36.8
Temperature Range:
Rated: –20 to 50°C | Maximum: –40 to 60°C Rated: –20 to 50°C | Maximum: –40 to 60°C
Listings/Certifications:
ETL listed to UL 1741 SA, CE, CSA C22.2 No. 107.1, UL 778 Annex F, IEC 62109-1 ETL, RoHS compliant per
directive 2011/65/EU, FCC Class B, IEEE 1574.1, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
ETL listed to UL 1741 SA, CE, CSA C22.2 No. 107.1, UL 778 Annex F, IEC 62109-1 ETL, RoHS compliant per
directive 2011/65/EU, FCC Class B, IEEE 1574.1, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
Non-Volatile Memory:
Yes Yes
Field Upgradeable Firmware:
Yes Yes
Chassis Type:
Vented Vented
03/2021
#980-00076-01-001 REV C
Instantaneous Power Rating: Most stringent, massive load start•GS8048A: 16970VA
Surge Power Rating: Less stringent load start•GS8048A: 12000VA
Peak Power Rating: Frequent “heavy duty” load requirements•GS8048A: 9000VA
Continuous Power Rating: Sustained “real world” load requirements•GS8048A: 8000VA
Radian GS8048A Power Rating
Power (VA)
20000
15000
10000
5000
0
100ms 5 sec 30 min Continuous
16970VA
12000VA
9000VA
8000VA
Typical Efficiency Rating: Real world efficiency with variable loads•GS8048A: 93%
CEC Efficiency Rating: Most stringent US rating•GS8048A: 92.5%
Radian GS8048A Efficiency Rating
Efficiency
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
93% (TYPICAL)
2kVA 4kVA 6kVA 8kVA
92.5%
(CEC)
INVERTING SELLING
Power Rating Notes: Inverters that specify power in VA but do not use the unity standard
Power Factor (PF) could have misleading power specifications. Volt-amps (VA) is a total
inverter output, while watts (W) represent the power consumed by the electrical loads. PF,
which varies by types of loads, is the ratio of W to VA, and the difference between the two is
power in the circuit that does no useful work. At 1.0PF (unity), all power is used. This is the
industry standard used by OutBack Power
.
Radian GS8048A Power Factor
Power Factor
8.0kVA 8.0kW 8.0kVA
6.8kW
1.0
0.75
0.5
0.25
0.0
0.85
Industry Standard Non-Industry Standard