Installation Guide
27
Meter connections
should be wrapped with self-bonding silicone tape, beginning on the jacket and ending on
the nut of the HOME-FLEX® tting.
If HOME-FLEX® tubing is installed in an exposed condition alongside a structure between the
ground and a height of 6 feet, the tubing should be installed in a location such that it won’t
be subjected to mechanical damage, or be protected inside a conduit.
HOME-FLEX® should never be buried directly underground. To route HOME-FLEX® tubing
underground, it must be protected within a nonmetallic water-tight conduit that is at least
½" larger than the outer diameter (OD) of the CSST tubing. Fittings and joints are not permis-
sible in such runs—the run must be one unbroken line of tubing. Runs underneath slabs
must be sleeved and vented per local codes. (See Section 4.9, “Underground Installations”
on page 33)
Note: If installed underneath mobile homes or in crawl spaces, HOME-FLEX® should be
installed in accordance with the above Outdoor Installation Issues section.
4.4 Protection
Protection is required when HOME-FLEX® tubing is concealed, constrained, and within 3
inches of a potential threat.
HOME-FLEX® exible gas tubing must be adequately protect-
ed wherever it is at risk of damage from puncture, shearing,
crushing, or other physical threats. Tubing is to be protect-
ed at support points, and when passing through structural
members of the building such as studs, joists, and plates as
outlined in this section. If the tubing requires protection, the
measures in this section should be followed.
Striker Plates
Shielding devices (striker plates) are used to protect the
HOME-FLEX® tubing from puncture threats such as drill bits,
nails, screws, etc. Such devices are required when the tubing
is concealed and is constrained such that the tubing would
not be able to move if struck by a puncture threat.
1. At support points and areas of possible penetration less
than 2 inches away from any edge of a stud, joist, plate, etc., shielding is required both at
the area of support and within 5 inches of each side. (Figure 4.9)
2. At support points and points of possible penetration 2-3 inches from any edge of stud,
joist plate, or other member, shielding is required throughout the area of support. (Fig-
ure 4.10)
3. At termination points
using the HOME-FLEX®
termination ange,
HOME-FLEX® Flexible
Protective Conduit
should be installed to
protect the CSST in
the area between the striker plates and the outlet. (Figure 4.11)
4. For tubing routed horizontally between studs, striker plates should be installed at each
stud, and Flexible Protective Conduit, or other approved conduit, should be installed
across the entire length of the run.
5. If striker plates can’t reasonably be installed (like between oors with enclosed joist areas
or installations when walls are already in place), schedule 40 steel pipe has been found
Figure 4.9 Elevated View of Unsupported
Horizontal Tubing Run
3
1
⁄2"
5"
Protected Area
Protected Area
Outside
Wall
Support
Adequate
Distance for
Escape
Non-Restrained Length
(Safe From Puncture)
Less than 2"
5"
5"
26"
Figure 4.10 Shielding at Support Area When Penetration is 2-3 inches from Edge
Support Joist
Striker Plate
Between 2-3"
Typical Wall Stud
(Wood or Metal)
Termination
Outlet (Stud
Mounted)
Stripwound
Metal Hose
Striker Plate
Interior Wall
3-1/2"
Less than 2"
Figure 4.11 Use of Flexible Protective Conduit
Striker
Plate
Less than 3"
Typical Wall Stud
(Wood or Metal)
Interior
Wall
Termination
Outlet (Stud
Mounted)
Flexible
Protective
Conduit
3
1
⁄2"
acceptable by CSA International for puncture protection. Steel pipe must have an inner
diameter at least ½" larger than the outer diameter of the HOME-FLEX® tubing (Table 4.4).
Protection must extend 5 inches beyond the pene-
tration of the structural members. A 12 inch pipe
length is acceptable for penetration of a single stud.
Despite this approval, the use of striker plates is rec-
ommended whenever possible.
Avoiding Puncture Threats
The best way to protect from puncture threats (and
potentially speed your installation) is to route tubing in
areas of the structures where no added protection is nec-
essary. The guidelines below will help the installer route
HOME-FLEX® tubing in areas where secondary puncture
protection isn’t required:
1. Support tubing such that it is more than 3 inches
away from any outside edge of a stud, joist, plate,
etc., or wall surface. (See Figure 4.12 compared to
Figure 4.10)
2. In non-restrained installations, make sure that the
tubing can move at least 3 inches from the direction
of potential penetration.
3. Tubing supported under joists in base-
ments or crawl spaces does not require
added protection so long as it is not con-
cealed by wallboard or ceilings and is at
least 3" away from puncture threats
through oors or ceilings.
4. Added protection is not necessary in unnished garage walls where the tubing is clearly
exposed so long as puncture threats do not exist from the outside wall.
Through-Wall Penetration
HOME-FLEX® tubing and its polyethylene jacket have been tested to the ame spread and
smoke density requirements of ASTM E84 and meets AGA and ANSI LC-1 limits imposed for
this criteria. HOME-FLEX® is classied as NFPA Class A/IBC Class A with a ame spread value
of 0 and a smoke density value of 80. Other requirements for re rated resistive constructions
may be imposed by local codes. The Qualied Installer must meet local building codes per-
taining to ame and smoke density regulations for nonmetallic materials at all times.
4.5 Meter connections
Natural gas meters are generally structurally supported independent of the building struc-
ture and piping system. When the gas meter is independently supported, HOME-FLEX® can,
in some localities, be used to connect the meter to the building gas system. If the gas meter
is not supported independent of the building structure or gas piping system, HOME-FLEX®
tubing cannot be used to connect directly to the meter.
Table 4.4 Steel Pipe Size for Puncture Protection
HOME-FLEX® Size Sch 40 Steel Pipe Size
½" 1¼"
¾" 1½"
1" 1¾"
Figure 4.12 Penetration Point Greater than 3" from Edge of Stud, Joist, Plate, etc.
Floor
Support Joist
Greater than 3"
Greater than 3"