Installation Guide
28
Installation Practices
Connection by Special Termination Fitting
Do not use HOME-FLEX® CSST as a direct connection if the meter must be supported by the
piping system. If the meter is supported by the building structure, common practice is to
route the CSST system to a termination ange mounted to the exterior of the building, and
to connect the meter to the termination ange with rigid pipe. Alternatively, rigid pipe can
be used to penetrate the building, with an attachment to HOME-FLEX® inside the structure.
(Figure 4.13)
Direct Connection
If a direct connection from HOME-FLEX® to an independently supported gas meter is permit-
ted by the local utility, the connection should include an extra 3-6" of length to allow for
building settling and meter movement. Exposed sections of CSST are to be wrapped with
self-bonding silicone tape, especially if the building is of masonry construction. For direct
connections through masonry construction, a PVC sleeve is required, and also recommended
for wood frame construction. (Figure 4.14)
Note: Check with the local servicing utility prior to directly connecting HOME-FLEX® to the
gas meter as utilities regulate connections to meter attachments.
4.6 Appliance connections
Termination Fittings with Appliance Connectors
The HOME-FLEX® termination ange tting is designed to service moveable appliances and
quick-connect devices at oor and hallow wall piping outlets (Figure 4.15) in combination
with a HOME-FLEX® Flexible Appliance Connector or similar approved device. The termina-
tion outlet minimizes the need
for concealed ttings and makes
the installation of gas connec-
tions for moveable appliances
easy. The ange plate should be
securely fastened in place during
rough-in of the structure. It may
be attached to a brace spanning
between wall studs or directly to
the oor.
As an alternative to the special
termination ange, a termination
can be made with rigid pipe con-
nected to the main HOME-FLEX® system. The rigid stub-out must be fastened to the wall or
oor using a pipe ange or other rigid mounting object.
Figure 4.13 Connection to Building supported Meter
Sleeve
(if required)
Sealant
(typical)
Termination
Fitting
Service Line
Meter
House Service
Regulator
Note: Diameter of hole shall
be at least 1/2" greater
than OD of tubing nad shall
be sleeved in accordance
with local building code (if
applicable).
Figure 4.14 Independently Supported Meter
Sealing
Radius of 3-6"
Figure 4.15 HOME-FLEX® Connection to Moveable Gas Appliance
Moveable
Appliance
Shut-off
Valve
Termination
Fitting
Flexible Protec-
tive Conduit
Mounting
Brace
HOME-FLEX
®
Appliance
Connector