Installation Guide

28
Installation Practices
Connection by Special Termination Fitting
Do not use HOME-FLEX® CSST as a direct connection if the meter must be supported by the
piping system. If the meter is supported by the building structure, common practice is to
route the CSST system to a termination ange mounted to the exterior of the building, and
to connect the meter to the termination ange with rigid pipe. Alternatively, rigid pipe can
be used to penetrate the building, with an attachment to HOME-FLEX® inside the structure.
(Figure 4.13)
Direct Connection
If a direct connection from HOME-FLEX® to an independently supported gas meter is permit-
ted by the local utility, the connection should include an extra 3-6" of length to allow for
building settling and meter movement. Exposed sections of CSST are to be wrapped with
self-bonding silicone tape, especially if the building is of masonry construction. For direct
connections through masonry construction, a PVC sleeve is required, and also recommended
for wood frame construction. (Figure 4.14)
Note: Check with the local servicing utility prior to directly connecting HOME-FLEX® to the
gas meter as utilities regulate connections to meter attachments.
4.6 Appliance connections
Termination Fittings with Appliance Connectors
The HOME-FLEX® termination ange tting is designed to service moveable appliances and
quick-connect devices at oor and hallow wall piping outlets (Figure 4.15) in combination
with a HOME-FLEX® Flexible Appliance Connector or similar approved device. The termina-
tion outlet minimizes the need
for concealed ttings and makes
the installation of gas connec-
tions for moveable appliances
easy. The ange plate should be
securely fastened in place during
rough-in of the structure. It may
be attached to a brace spanning
between wall studs or directly to
the oor.
As an alternative to the special
termination ange, a termination
can be made with rigid pipe con-
nected to the main HOME-FLEX® system. The rigid stub-out must be fastened to the wall or
oor using a pipe ange or other rigid mounting object.
Figure 4.13 Connection to Building supported Meter
Sleeve
(if required)
Sealant
(typical)
Termination
Fitting
Service Line
Meter
House Service
Regulator
Note: Diameter of hole shall
be at least 1/2" greater
than OD of tubing nad shall
be sleeved in accordance
with local building code (if
applicable).
Figure 4.14 Independently Supported Meter
Sealing
Radius of 3-6"
Figure 4.15 HOME-FLEX® Connection to Moveable Gas Appliance
Moveable
Appliance
Shut-off
Valve
Termination
Fitting
Flexible Protec-
tive Conduit
Mounting
Brace
HOME-FLEX
®
Appliance
Connector