User manual

79
For a temperature of less than -5.0 °C or more than +25.0 °C, the “GX107” will trigger an alarm.
The threshold setting area can be set from -400 to +1250.
If “Temp1” is set to = +1250, the top threshold is deactivated.
If “Temp2” is set to = -400, the lower threshold is deactivated.
Indication of prefixes “+” and “-” before the figures is mandatory. Without the
corresponding prefix, and error will be output.
An error will also be output if the value of “Temp2” is larger than “Temp1”.
Deleting the set thresholds
To delete the set thresholds, use the command:
RESET TEMPERATURE #1513
Checking settings
To verify the present settings, use the command:
TEST TEMPERATURE #1513
Hysteresis function:
As of firmware version 1.11d (the version number is in every answering text message), every
analogue measurement (ADC, TEMPERATURE, VOLTAGE) has a hysteresis to prevent
multiple alarms in case of measured value fluctuations around the alarm value. Please observe
the corresponding chapter “Hysteresis”.