Specification

49
800-757-6996
AC CABLES
Armor & Jacket
Aluminum Interlocked (Green Striped) with ColorSpec
®
ID
Conductors
Solid/Stranded Copper (See Below)
Conductor Insulation
THHN
Conductor Insulation Covering
Moisture Resistant Fire Retardant Paper Wrap
Maximum Temperature Rating
90°C (Dry) Type ACTHH
Grounding
16 AWG Integral Bond Wire/Armor Combination per 250.118(8) and Green Insulated
Copper Grounding Conductor per 250.118(1)
Neutral Conductor
White 120/208V
Gray 277/480V
Maximum Voltage Rating
600V
References & Ratings
UL 4, 83, 1479, 1581, 2556, File Reference E7330
NEC
®
250.118(8), 300.22(C), 392, 320, 517.13, 518, 645
Federal Specification A-A-59544 (formerly J-C-30B)
Meets all applicable OSHA and HUD Requirements
Cable Tray Rated, install per NEC
®
UL Classified 1, 2, and 3 hour through (Fire) penetration product, R14141
Environmental Air-Handling Space Installation per NEC
®
300.22(C)
Aluminum armored cables are RoHS Compliant
U.S. Patent No. 8,278,554 B2
Made in USA of US and/or imported materials
HCF®-Lite Aluminum Healthcare Facilities Cable
Type AC (120/208V & 277/480V) Technical Specifications
Product Code Stock Items
Trade Size
Grounding
Conductor AWG
Length (ft)
Approx. Weight/
1,000ft (lbs)
Approx. Armor O.D.
(in)
Coil Reel Coil Reel
HCF® Lite Aluminum Healthcare Facilities Cable
120/208V
2804G42-00 2804G60-00 12-2 Solid (Black, White) 12 Solid (Green) 250 1000 132 0.535
2805G42-00 2805G60-00 12-3 Solid (Black, Red, White) 12 Solid (Green) 250 1000 171 0.625
2806G42-00 2806G60-00 12-4 Solid (Black, Red, Blue, White) 12 Solid (Green) 250 1000 195 0.610
2807G42-00 2807G60-00 10-2 Stranded (Black, White) 12 Solid (Green) 250 1000 185 0.599
2808G42-00 2808G60-00 10-3 Stranded (Black, Red, White) 12 Solid (Green) 250 1000 232 0.653
2809G42-00 2809G60-00 10-4 Stranded (Black, Red, Blue, White) 12 Solid (Green) 250 1000 279 0.752
120/208V Stranded
2858G42-00 2858G60-00 12-2 Stranded (Black, White) 10 Stranded (Green) 250 1000 141 0.568
2859G42-00 2859G60-00 12-3 Stranded (Black, Red, White) 10 Stranded (Green) 250 1000 171 0.594
2860G42-00 2860G60-00 10-2 Stranded (Black, Red, Blue, White) 10 Stranded (Green) 250 1000 211 0.695
120/208V Specialty Colors
2804G42-04 2804G60-04 12-2 Solid (Red, White) 12 Solid (Green) 250 1000 132 0.535
2804G42-05 2804G60-05 12-2 Solid (Blue, White) 12 Solid (Green) 250 1000 132 0.535
480Y/277V
2804G42-01 2804G60-01 12-2 Solid (Brown, Gray) 12 Solid (Green) 250 1000 132 0.535
2804G42-02 2804G60-02 12-2 Solid (Orange, Gray) 12 Solid (Green) 250 1000 132 0.535
2804G42-03 2804G60-03 12-2 Solid (Yellow, Gray) 12 Solid (Green) 250 1000 132 0.535
2805G42-01 2805G60-01 12-3 Solid (Brown, Orange, Gray) 12 Solid (Green) 250 1000 171 0.625
2806G42-01 2806G60-01 12-4 Solid (Brown, Orange, Yellow, Gray) 12 Solid (Green) 250 1000 195 0.610
NOTE: All dimensions and weights are subject to normal manufacturing tolerances.
Not to be used with set screw type fittings or on DC circuits.
Sizes 14 AWG, 8 AWG, & larger are available by special order and subject to lead time and minimum quantities
Not to be used with setscrew type fittings or on DC circuits
See page 61 for bond wire termination details.
Emergency circuits require special consideration in healthcare settings.
Review NEC® 517.30 (C)(3)(3) for guidance on the use of HCF cables on emergency circuits.
Green Insulated
Copper Ground
Nylon Thermoplastic
THHN Insulation
Interlocked Aluminum Strip
(Color-Coded Green)
Bare Aluminum
Bonding Wire
Insulated Bushing
Paper Wrap on
Each Conductor
49
AFC Cable Catalogwww.afcweb.com

Summary of content (1 pages)