Adjusting the Rain Sensor Threshold
e Weather Sensor is preset to suspend watering at 1/4” (6 
mm) of accumulated rainfall. ree alternate settings of 1/8” (3 
mm), 1/2” (12 mm) and 3/4” (19 mm) are provided. Prior to 
installing the Weather Sensor, adjust the threshold to the 
preferred setting as required.
  Increasing the threshold setting results in extending 
the length of time required for the sensor to shut o or 
postpone watering during rain. is will also postpone 
when the dry out period commences and scheduled 
watering will resume. In areas where heavy fog or mist 
is common, the 1/8” (3 mm) setting may trigger false 
readings and suspend irrigation. It is recommended that a 
higher setting is used in these areas.
1.  Turn the cap slightly, releasing it from the two retaining pins. 
2.  Adjust the cap to engage the pins at the preferred slot setting.
The Weather Sensor
!
 Important: e Weather Sensor must have full exposure 
to sun, wind and rain, and must not be installed inside a rain 
gutter, or in any location where immersion, runo, or contact 
with irrigation spray will occur. Avoid installating near a heat 
source, such as a heater vent or chimney. Also avoid installation 
near any large metal structure or high current-draw equipment 
that may generate signal interference. Ensure the antenna wire 
hangs unobstructed below the Weather Sensor.
  e communication range of the Wireless Weather Sensor 
system is 1000’ (305 m) LOS (line of sight). Some loss of 
range can be expected due to interference from obstacles 
in the signal path. Test the signal reception from the 
proposed installation site prior to mounting the Weather 
Sensor, as described in the following procedure. 
1.  Start a manual watering operation for a zone that can be 
seen from the proposed Weather Sensor location. Press and 
hold the Rain Sensor test pin to send a signal to the Smart 
Connect. If the signal is received, watering should shut o 
within a short time. If not, repeat the test from a dierent 
location until communication is established.
1/4” (6.4mm)
1/2” (12mm)