Valve, Pump Relay and Sensor Installation
 Figure 13
1 2
MV PUMP
SENSOR
SENSOR
COM
COM
Step  1  –  Route valve wires from the valves, master valves, pump relay and/or sensor into the controller cabinet.
 Note: 18 AWG (1.0 mm
2
) multi-wire sprinkler valve connection cable can be used. is cable is insulated for direct burial 
and is color-coded to simplify installation. It can be routed directly into the controller through the access hole provided for 
valve wire conduit (if conduit is not used).
Step  2  –  Connect valves, master valves and pump start relay to the valve wires - Connect the white color-coded wire from the cable 
to one wire from each valve solenoid and/or pump relay. (Either of the two wires from the solenoid or pump relay can be used 
for this connection.) is connection will be designated as the valve common wire. 
Connect a separate cable wire to the remaining wire from each valve solenoid. Note the wire color-code used for each valve and 
the zone it controls. You will need this information when connecting the valve wires to the controller.
Step  3  –  Secure all wire splices using wire nut connectors. To prevent corrosion and possible short circuits, always use an insulated wire 
nut, grease cap or similar waterproong method.
Step  4  –  Connect valves wires to the controller - Secure the valve common wire (white) to either of the two terminals labeled COM. 
Secure the individual valve wires to the appropriate zones they control, Zone 1 valve to terminal 1, Zone 2 valve to terminal 2, etc.
Step  5  –  Connect master valve/pump relay wires to the controller - Secure the valve common wire (white) to either of the two 
terminals labeled COM. Secure the Master Valve or Pump Relay wire to the terminal labeled MV/PUMP.
Caution: To prevent controller damage, do not connect the pump motor starter directly to the controller.
Step  6  –  Connect sensor wires to the controller - Remove the jumper wire from the SENSORS terminals. Secure the two sensor wires 
to the sensor terminals. Refer to the provided sensor instructions for further installation instructions. 
EVOLUTION
®
 is designed to operate with “normally closed” NC sensors.
     Note: For sensors with “normally open” (NO) and “normally closed” (NC) options, select the NC option.
Step  7  –  Test for proper operation.