Use and Care Manual

1-550.28
4
Figure 4.3 - Horizontal Unit Delivery
Figure 4.3 - Vertical Cone Jet
Figure 4.4 - Vertical One-Way & Two-Way Louvers
H
H
H
H
H
1.3
1.2
1.1
1.0
.9
.8
.7
.6
.5
Correction Factor "R"
150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370
Average Water Temp – F
Steam Pressure
25 10 20 30 50 70 100
150
With horizontal louvers opened 30° from the vertical plane. HSB units have top and bottom piping connections, HC units have side connections. All have copper tubes.
V and PT models have copper tubes, VN and PTN models have cupronickel tubes. Mounting heights are maximum for heaters operating at standard conditions
(2 lbs. steam or 220°F water with 60°F entering air). Heights listed for Louver or Cone-Jet are with deflectors in fully-opened position. Refer to Figure 4.2 for correction of
mounting heights under other operating conditions. Maximum mounting height will be reduced as entering air temperatures exceed 60°F.
These correction factors are to be used as multipliers to correct the maximum recommended mounting heights of unit heaters when operated with steam pressures other
than 2 pounds or with water at other than average temperature of 220°F.
UNIT MOUNTING
Figure 4.2 - Maximum Mounting Heights Correction Factors
H
Figure 4.6 - Vertical Truncone
With horizontal louvers opened 30° from the vertical plane. HSB units have top and bottom piping connections, HC units have side connections. All have copper tubes.
V and PT models have copper tubes, VN and PTN models have cupronickel tubes. Mounting heights are maximum for heaters operating at standard conditions
(2 lbs. steam or 220°F water with 60°F entering air). Heights listed for Louver or Cone-Jet are with deflectors in fully-opened position. Refer to Figure 4.2 for correction of
mounting heights under other operating conditions. Maximum mounting height will be reduced as entering air temperatures exceed 60°F.
Horizontal Type Power-Throw Type
Vertical Type with Deectors
No Deector Cone-Jet Truncone Louvers
Model No.
Height (ft)
Model No.
Height (ft)
Model No.
Height (ft) Height (ft) Height (ft) Height (ft)
Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T.
HSB/HC 18 8 9 V/VN 42 11 13 15 17 8 9 13 15
HSB/HC 24 9 11 V/VN 59 14 16 19 22 9 11 16 18
HSB/HC 33 10 12 V/VN 78 15 19 20 26 11 14 17 22
HSB/HC 47 12 14 V/VN 95 15 19 20 26 11 14 17 22
HSB/HC 63 14 16 V/VN 139 18 23 24 31 13 17 21 26
HSB/HC 86 15 17 V/VN 161 20 26 27 35 14 18 23 30
HSB/HC 108 17 19 V/VN 193 22 27 30 36 16 19 25 31
HSB/HC 121 16 18 V/VN 212 22 27 30 36 16 19 25 31
HSB/HC 165 19 21 V/VN 247 26 32 34 42 17 21 30 37
HSB/HC 193 18 PT/PTN 279 16 V/VN 279 30 36 37 45 18 22 35 41
HSB/HC 258 19 22 PT/PTN 333 17 V/VN 333 30 36 37 45 17 20 35 41
HSB/HC 290 20 23 PT/PTN 385 17 V/VN 385 30 36 36 43 17 20 35 41
HSB/HC 340 20 23 PT/PTN 500 18 V/VN 500 37 45 44 54 19 24 42 51
PT/PTN 610 20 22 V/VN 610 36 44 43 52 19 24 41 50
PT 952 21 V 952 37 45
Table 4.1 - Maximum Mounting Heights