ELECTRICAL CONNECTIONS
DANGER: Risk of severe injury from electric shock or death by electrocution. This bath must be must be connected directly to a dedicated
120V 15 amp supply circuit that is protected by a Ground Fault Circuit Interrupter (GFCI) installed by a qualied, licensed electrician in
accordance with national electric and local codes and the GFCI manufacturer’s instructions. The GFCI should be tested regularly. To test
the GFCI, push the “TEST” button. The GFCI should interrupt the power supply to the outlet. Push the “RESET” button and the power
should be restored. If the GFCI fails to operate in this manner, it is defective. If the GFCI interrupts power without pressing the “TEST”
button, a ground current is owing indicating the possibility of electric shock exists. DO NOT USE. Disconnect the unit and have the
problem corrected by a qualied licensed electrician before using.
The GFCI is not included with the bath. The circuit must be a (3) three-wire circuit hard wired from the main power supply. Install the
outlet on the stud wall at least 4” above the oor. Your bath is equipped with a 36” cord with a grounded plug on the blower. Do not
remove the grounding pin or alter the cord in any way.
Important: Unauthorized modication may cause unsafe operation and poor performance. Moving components or making modications
may adversely aect performance and make operation unsafe. Signature Bath shall not be liable under its warranty of otherwise for
personal injury or damage that is the result of unauthorized modication.
Important: Risk of overheating. Cord must be plugged directly into the GFCI. Do not use an extension cord or surge protector.