Piping System Applications
>> Maximum Working Temperature
180° F (82° C)
>> Maximum Working Pressure
400 PSI at 73° F
100 PSI at 180° F
>> Joining Method
Solvent Weld Joints
Solvent cements must meet ASTM F 493.
Yellow FlowGuard Gold cements may be used
without primer, where approved by code.
Compression fittings with a brass ferrule
may be used.
Threaded Joints
Threading the pipe is NOT recommended
Use CPVC CTS male adapters in cold water
applications only.
Use CPVC CTS x brass threaded transition
fittings for hot water applications.
Do NOT use compression fittings with
brass ferrules to connect to CPVC CTS
pipe or fittings where water temperatures
will exceed 140° F.
CPVC CTS pipe can be used with standard
brass ferrules to make compression
connections where the operating temperature
will NOT exceed 140° F. Apply Teflon
(PTFE) tape over the ferrule to allow for
the dissimilar thermal expansion and
contraction characteristics of the metal
ferrule and the plastic pipe.
FlowGuard Gold
®
CPVC Copper Tube Size (CTS) Pipe & Fittings
For Pressurized Hot & Cold Water Applications
FlowGuard Gold CPVC CTS Pipe & Fittings