Installation Guide

3
Installation S19-270B
Bradley Corporation 215-634 Rev. V; ECM 11-05-004 5/16/11
Installation
Supplies Required:
• Pipesealant
• Pipingto½"NPTwatersupplyinletonunit
• Sign-mountinghardware
NOTE: Local codes may require the installation of a backflow prevention valve to complete proper installation. Compliance
with local codes is the responsibility of the installer. Valve must be tested annually to verify that it is functioning properly.
Backflow prevention valves are not included with the fixture and may be supplied by the contractor or purchased from
Bradley Corporation.
Step 1: Attach eyewash
NOTE: The top of the eyewash heads should be positioned a maximum of 45" from the floor.
1. Selectthedesiredlocationfortheeyewashonthesinkdeckanddrilla
7
8"diameterhole.
2. Securetheassembledunittothedeckwiththenutandwasherprovidedasshownonpage4.
Step 2: Connect water supply
1. Connectthewatersupplyusing¼"nominal(
3
8"O.D.)coppertubing(suppliedbyinstaller),thefrictionring,seal
washerandnutprovided.
2. Mountthesafetysigntowallorpipeusingsign-mountinghardwaresuppliedbyinstaller.
3. Openthewatersupplylines.Testforleaksandadequatewaterflow.
Ø 2½"
(63mm)
36" (914mm)
to Finished Floor
12"
(305mm)
5
3
8"
(137mm)
8
3
8"
(113mm)
2¾"
(70mm)
max. deck
thickness