Instructions / Assembly

18
YES
CAUTION
!
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERIFY PROP-
ER OPERATION AFTER SERVICING!
Section 3... the “IGNITION” LED
“System Sentinel” Troubleshooting Guide
Did the Damper Assembly
fully open?
Check Damper for obstruc-
tions—remove if necessary.
Did Damper fully open?
Is 24 VAC power present
between the Blue and Gray
wires in the Polarized Plug at
Damper Assembly?
1. Remove Ignition Cable and check for good
continuity, replace if necessary.
2. Check Ignitor Electrode gap for proper
spacing (1/8” to 5/32”). Correct if necessary.
3. Examine Ceramic Insulator on Pilot Assem-
bly for cracks. Replace if cracks are evident.
If all of the above components check okay,
replace Ignition Control Module.
Is 24 VAC present between the
Gray ground wire and the Red 24
V wire connected to the Ignition
Control Module?
Check continuity of Red
and Gray wires between
Damper Assembly and Igni-
tion Control Module. Is con-
tinuity “good”?
Remove Damper Drive
Motor cover; is the green
“CALL FOR HEAT” LED
illuminated?
Damper Assembly is defective and must be replaced. The water heater may still be used until a replacement Damper Assembly can be
installed by following these steps:
Turn off power to the water heater at the main power switch located on the side of the control enclosure. Order a replacement Damper Assembly. With power still off,
remove Damper Drive Motor cover and move the Service Switch located to the right of the the motor from the ”NORMAL” position to the ”SERVICE” position. Using a stan-
dard flat screwdriver, rotate the slotted white knob, located below the motor, counter-clockwise until the damper blade is in the open (fully vertical) position. Replace cover
and turn power on at the main power switch located on the side of the control enclosure. The heater should now attempt its firing sequence.
* Denotes these boxes are for use with the “Power Assist Burner & Xtreme models” only.
Is Spark Ignitor operating?
(Can sparking be heard?)
The System Sentinel Panel is
defective and must be replaced.
Repair or replace the Wiring Har-
ness
Refer to Troubleshooting
Guide, Section 2...the “THER-
MOSTAT” LED to determine if
Thermostat is operable. Repair
or replace if required.
Ignition Control Module is defec-
tive and must be replaced.
The Thermostat has called for
heat, the Damper Assembly has
fully opened, and 24 VAC power is
being supplied to the Ignition Con-
trol Module and the ignition
sequence will begin.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Is the “IGNITION” LED Illuminated?
Is the green “IGN GAS
PWR” LED illuminated?
*Is 24 VAC present
across coil of relay?
*Is blower operating?
*Relay is defective
and must be replaced.
*Blower is defective
and must be replaced.
*Relay is defective
and must be replaced.
*Pressure switch is
defective and must
be replaced.
*Pressure switch is
defective and must
be replaced.
*Is there continuity
across normally
closed pole and
common pole of
pressure switch?
*Is there 120 VAC
across Brown wire
and Blue wire of
blower?
*Is there 24 VAC
present between
the common pole
and the normally
open pole of the
pressure switch?
NO
YES