TDC-100/200 Stand-Alone Model User’s Guide
Table of Contents Introduction ..... ......................................................................................... 3 General Editing .......................................................................................... 3 Timing Mechanism Components ............................................................... 4 Mother Board Components ....................................................................... 5 Daughter Board Components ...................................................
Introduction The Toro TDC-100/200 system combines modular flexibility, ease of use and increased programmability in a single controller. Modularity means flexibility. The TDC-100/200 can control up to 200 stations. The TDC system uses innovative technology to provide an irrigation solution that is safe, reliable and energy efficient.
Timing Mechanism TDC-100/200 3 2 1 4 5 6 HOME 10 11 %ADJUST 7 8 MANUAL WATERING SCHEDULED WATERING DIAGNOSTICS START PAUSE/ RESUME STOP 12 13 9 STATION SETTINGS 14 SYSTEM SETTINGS 1. Left and Right Arrows allow you to select the next entry field within the same menu line. Any changes will be saved after you exit that entry field. 2. Up and Down Arrows allow you to scroll up and down through the menu items. 3. LCD Panel is the display screen. 4.
Power-Up Diagnostics Upon power-up, the controller will display: Rev: 02.08, 06/25/11 GDC–200 System Booting Detecting Stations PD 05/15/11 10:51:20 The TDC-100/200 will initiate a diagnostic test automatically during power-up. This function will take approximately ten seconds and it cannot be bypassed. If a problem is detected during the diagnostic test, it will be indicated on the display. When completed, information will be displayed momentarily on the screen for five seconds.
1 2 Mother Board 3 7 6 8 4 5 13 12 11 10 9 14 Daughter Board Mother Board Components 15 1 Mother Board Diagnostic Display 2 Timing Mechanism Cable Socket 3 Pressure Sensor Terminals 4 Rain Sensor Terminals 5 Flow Sensor Terminals 6 Master Valve / Pump Terminals 7 Toro Maintenance Remote (TMR) Receiver Socket 8 24 VDC (power access for optional accessories) 9 RS-232 Receiver (Used for PC Mode Communication.) 10 USB Device Input (Used for PC Mode Communication.
Note: Program stacking occurs when the controller is running a program where the maximum simultaneous station limit is surpassed. Additional scheduled programs will be stacked (delayed) until an available station can be activated. System Settings System Settings allows you to set controller parameters such as Time, Date and Language. Use the up or down arrow keys Use the left and right arrow keys Use the input dial Hold For: – to navigate through the menus.
Display Adj: – Reset Sta’s: – Use this function to reset all station settings by selecting Yes. After selecting Yes, press the up or down arrows to activate. The following will display: Use this function to adjust the contrast of the LCD screen. Use the input dial darken or lighten the text display. to Reset All Stations to defaults 05 STOP to escape All station settings will be erased after a successful reset.
Station Settings Station Settings allows you to set parameters specific to each station. Use the up or down arrow keys Use the left and right arrow keys Use the input dial to navigate through the menus. to advance to the next entry field on the same menu line. to select values when editing. S001 – Select the station you want to edit in this field. Choose from Station 001 through the controller maximum station count of 200.
Scheduled Watering The TDC-100/200 features 10 fully-independent resident programs. With two types of programs to select from, you can further custom fit your irrigation programs to any landscape. • Standard Irrigation Program will activate a station or group of stations with six start times on a daily basis. Each station will water for the duration specified in hours, minutes and seconds. Percent adjust and maximum number of simultaneous activate stations per program can be specified in this program.
8. Press the down arrow key to advance the cursor to the Sta Dly: field. Use the left and right arrow keys to navigate between the Hour and Minute fields. Use the input dial to set the Station Delay duration. Station delay is the wait period when a station finished watering and when the next station is activated. In most situations, station delay is used to allow slow -shutting valves time to fully close before activating another station and also to allow the water source, such as a well, to recover.
Grow In Irrigation Program Setting: Grow In Irrigation Program example: Create program 3 with stations 21–30 for 5 minutes each with no percent adjustment. Set the start time at 6:30 am and the end time at 4:00 pm. Set the delay for 2 hours and 15 minutes and the maximum simultaneous active station to 5. 1. Press the Scheduled Watering key . The cursor is initially located at the program selection field. Use the input dial to select the program (P01–P10) you want to create or modify.
Manual Watering The Manual Watering functions are used for additional watering if the irrigation program is not sufficient. They can also be used to troubleshoot each station for proper operation. Pressing the Manual Watering Key will access three manual irrigation functions; Multi-Manual, Syringe and Program. M-Manual - Select M-Manual to activate a station or group of stations with a specified runtime.
Syringe - Choose Syringe to activate all the stations in a selected irrigation program for a specified runtime. Note: The Maximum number of simultaneous stations set in the program still applies. Manual Syringe Activation Directions Syringe activation example: Manually activate all the stations in Program 3 for 2 minutes each. Note: An irrigation program must be configured to activate Manual Syringe. 1. Press the Manual Watering key . 2. The cursor should be located in the Manual field.
% (Percent) Adjust The percent adjust function allows you to fine tune irrigation programs. With weather conditions changing constantly, Percent Adjust allows you to easily adjust your system’s schedules without modifying the program values. Important: The percentage settings do not override each other, instead, they multiple each other to get the effective adjustment. Example: Controller’s Global% is set at 150%, Program% is set at 125% and Station% is set at 90%.
Pause / Resume The Pause command is used to suspend active program or manual irrigation. The Pause function allows the user to specify the pause duration. Pause / Resume Function Directions Pause function example: Program 01 has been manually activated. Pause program 01 for 30 minutes. 1. Press the Pause key. 2. Use the input dial to select All, M-Man or Prg:XX (XX = the program number).
If a syringed program is on Pause All, activating a new pause for the same syringe program will overwrite the remaining pause time with the new pause time for that syringed program. Pause All All currently running programs, multi-manual and syringe will be suspended until the pause time-out expires. New start is allowed only for Manual functions. Additional programs that are scheduled to start while Pause All is in effect will be stacked until the Pause time-out expires.
Diagnostics The diagnostics function allows the user to monitor Radio Link status, check the firmware version, troubleshoot stations using the Sequence Stations options, monitor the system’s water usage, monitor all system’s sensor status, monitor system’s voltages, check alarm status, clear alarms and execute a self diagnostics to the system. Menu: Station Alarms S001 Alarms: 01 No Comm w/ Decoder 06/15/11, 10:07 Use this menu to check alarm codes that have been activated.
Mother Board Diagnostic Display The TDC-100/200 features a 2-line, 16 character LCD display for quickly viewing for system diagnostic information. Use the left button bellow the LCD to scroll through the display lines and if needed, use the right button to scroll through the available options. Screen Explanation Rev 2.02 03/28/2011 D1 A=1.500 D2 = OFF After power up, the screen will display board’s firmware version.
Alarm Conditions All of the Alarm Conditions, when active, toggle back and forth between the two message states below. Short Circuit Alarm D1 Short D2 A=0.500 Hold Opt to Clr D2 A=0.500 Thermal Alarm • • • • D1 Thermal D2 A=0.500 • • Hold Opt to Clr D2 A=0.500 • High Current Alarm D1 High Amp D2 A=0.500 D1 A=1.100 D2 A=0.500 Phase Current Imbalance Alarm D1L1 High Amp D2 A=0.500 D1L1 A=0.750 D2 A=0.500 • • • • • • • • • • 2.0 Amp Trigger Shuts off and disables daughter board indefinitely.